TEF 9207 Ex
ENCLOSURE HEATER USER MANUAL
TECHNICAL DATA
Housing Material:
Acid proof stainless steel
Heater cable overjacket material:
Fluoropolymer
T-rating:
T3 (Max. 200°C)
T
amb
:
-50°C - +50°C
Maximum withstand temperature
Power off:
+80°C
Degree of protection:
IP66
Electrical protection:
Use max. size of 16A circuit breaker
For use in zone:
Zone 1, Zone 2 and safe area
Compliance with:
EN 60079-0:2009 / IEC 60079-0:2007, EN 60079-7:2007 / IEC 60079-7:2006
EN 60079-18:2009 / IEC 60079-18:2009, EN 60079-30-1:2007 / IEC 60079-30-1:2007
CAN/CSA C22.2 60079-0:07 , CAN/CSA C22.2 60079-7:03 , CAN/CSA Standard C22.2 No. 0-M91
CAN/CSA Standard C22.2 No. 14-10 , CAN/CSA Standard C22.2 No. 130-03
CAN/CSA Standard C22.2 No. 213 - M1987(R2008)
ANSI/IEC 60079-7:03 , ANSI/IEC 60079-30-1:07 , ANSI/IEC 60079-0:07
ANSI/IEC 62086-1 (1st Edition) Part 1
IEC 62086-1 (1st Edition) Part 1
IEC 60079-30-1:07
ISA/ANSI 12.12.01-2011 UL 1693:11
L L
N
N
PE
PE
Electrical connection
Conductor cross-section
L/N: 0,2mm² - 6mm² AWG 24-10
PE: 0,5mm² - 10mm² AWG 20-8
920A106068
920A108158
ALT. POWER OUT
POWER IN
ALT. CABLE
CABLE
POWER OUT
EARTH BOLT
M6x10