In general, the FluidSecure LINK should control a solenoid valve, dispenser authorization
signal or a small pump motor.
Under no condition should a FluidSecure LINK control
a pump motor larger than 3/4hp.
Larger loads can be controlled with an external
contactor or power relay.
1) Conduit Connections between Pump and LINK
Installation for standard dispensers is quite simple. Most have an explosion proof
junction box located in the bottom section of the dispenser. This junction box generally
will have two or more conduits that feed into it. Normally there are additional available
conduit openings in the junction box. Simply unscrew the cap from one of the unused
ports and screw in the FluidSecure LINK. If there are no available openings you will have
to use a rated Class 1, Division 1, T box (or purchase the optional hardware kit) to attach
to the junction box and re-route an existing conduit to the box and then attach the
FluidSecure LINK. The manual override switch can be removed from the wiring
enclosure and inserted into an additional conduit opening in the junction box.
Manual Override Junction Box LINK