User Manual
TRAQC-5
P1000
TRAQC-5 P1000 & TRAQC-1 DPG rev.0
page : 36
16.8
Zero point correction (ZERO)
The zero point can be corrected manually should undesired deviations occur when no system
pressure is being applied (atmospheric pressure).
Caution!
The zero point correction sets the current ACT value to zero. In order exclude
erroneous measurements, ensure
no system pressure is being applied when carrying out this function.
This initiates the zero point correction.
The ACT (actual) value is indicated in the display as 0.0 bar.
The correction remains active until the device is turned off.
OFL/ZEro is displayed for 3 seconds if the
measured pressure (0 bar) is greater than 5% of
the measurement range.
Zero point correction cannot be carried out.
Please ensure that no system pressure is being
applied
.
16.9
Resetting the zero point correction
Turn off the device.
Zero point correction is no longer active when the device is turned off and on
again.