Tradewinds RNC5-TPD Скачать руководство пользователя страница 21

21

Poor Air Flow 

Supply air feels cold

Dehumidistat is not Operating

Humidity Levels are too High in Winter 
Condensation is appearing on the 
windows

Humidity Levels are too Low 

HRV and / or Ducts Frosting up

Condensation or Ice Build Up in 
Insulated Duct to the Outside 

Water in the bottom of the HRV 

20 Minute Timer Not Working

• 1/4” (6mm) mesh on the outside hoods is plugged
• filters plugged
• core obstructed
• house grilles closed or blocked
• dampers are closed if installed
• poor power supply at site
• duct is restricting HRV
• improper speed control setting
• HRV air flow improperly balanced

• poor location of supply grilles, the air flow may irritate

the occupant

• outdoor temperature extremely cold

• improper connection to ventilator
• external low voltage is shortened out by a staple or nail
• check dehumidistat setting it may be on OFF

• dehumidistat is set too high
.• lifestyle of the occupants

• moisture coming into the home from an unvented or

unheated crawl space

• moisture is remaining in the washroom/bathroom and

kitchen areas

• condensation seems to form in the spring and fall

• HRV is set at too low a speed

• dehumidistat control set too low
• blower speed of HRV is too high 
• lifestyle of occupants
• HRV air flow may be improperly balanced

• HRV air flow is improperly balanced
• malfunction of the HRV defrost system

• incomplete vapor barrier around insulated duct
• a hole or tear in outer duct covering

•  drain pans plugged
•  improper connection of HRV drain lines
•  HRV is not level
• drain lines are obstructed
•  HRV heat exchange core is not properly installed

• Wiring
• Faulty control
• Faulty circuit board

• clean exterior hoods or vents
• remove and clean filter
• remove and clean core
• check and open grilles
• open and adjust dampers
• have electrician check supply voltage at house 
• check duct installation
• increase the speed of the HRV
• have contractor balance HRV

• locate the grilles high on the walls or under the baseboards,

install ceiling mounted diffuser or grilles so as not to directly
spill the supply air on the occupant (eg. over a sofa)

•  turn down the HRV supply speed. A small duct heater     (1kw)

could be used to temper the supply air

• placement of furniture or closed doors is restricting themove-

ment of air in the home

•  if supply air is ducted into air handler return, the air handler fan

may need to run continuously to distribute ventilation air com-
fortably

• check that the correct terminals have been used
• check external wiring for a short
• set the dehumidistat at the desired setting

• set dehumidistat lower
• avoid hanging clothes to dry, storing wood and venting clothes

dryer inside. Heating wood may have to be moved outside

• vent crawl space and place a vapor barrier on the floor of the

crawl space

• ducts from the washroom/bathroom should be sized to remove

moist air as effectively as possible, use of a washroom/bath-
room fan for short  periods will remove additional moisture

• timer or fan can be added to washroom/bathroom exhaust
• on humid days, as the seasons change, some condensation

may appear but the home’s air quality will remain high with
some HRV use

• increase speed of the HRV

• set dehumidistat higher
• decrease HRV blower speed 
• humidity may have to be added through the use of humidifiers
• have a contractor balance HRV air flow

• Note: minimal frost build-up is expected on cores before

unit initiates defrost cycle functions

• have HVAC contractor balance the HRV
• ensure working properly.

• tape and seal all joints 
• tape any holes or tears made in the outer duct covering
• ensure that the vapor barrier is completely sealed

• ensure O-Ring on drain nozzle sits properly
• look for kinks in line
• check water drain connections
• make sure water drains properly from pan

• disconnect external controls and run unit through self test. If

the unit runs through self test successfully, then the circuit
board is okay.

• check wiring connection.
• make sure wires are connected to proper terminals.
• test 20 Minute Timer, press and hold the button for 10 seconds

then release. The unit should run on high speed and then return
to normal operation when the button is released.

Troubleshooting

Symptom

Cause

Solution

Содержание RNC5-TPD

Страница 1: ...air The HRV is equipped with an aluminum core The device uses the stale air that is being exhausted to con dition the fresh air as it is being brought in These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities who have jurisdiction before installation Shipping and Packaging List 1 Required Tools 1 Application 1 General 1 Engineering Data 2...

Страница 2: ...e DUCT CONNECTIONS 4 5 127 mm duct connections Weight 61 lbs 28 kg Shipping Weight 64 lbs 29 kg All units conform to CSA and UL standards 27 690 mm 15 378 mm 2 1 4 57 mm 18 3 4 475 mm SPEED SELECTION SWITCH TM HEAT RECOVERY VENTILATOR HEAT RECOVERY VENTILATOR Dimensions OPTIONAL ACCESSORIES 99 101 Crank Timer 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Cont...

Страница 3: ...rical box of HRV OFF Standby LOW or OFF HIGH speed operation is also available DUCT CONNECTIONS 4 5 127 mm duct connections Weight 61 lbs 28 kg Shipping Weight 64 lbs 29 kg All units conform to CSA and UL standards 27 690 mm 15 378 mm 2 1 4 57 mm 18 3 4 475 mm SPEED SELECTION SWITCH Dimensions 1 2 3 0 20 40 60 80 100 120 140 160 180 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1 Static Pressure in w ...

Страница 4: ...nded Weatherhood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weatherhood Requirements At least 6 2 m from the ventilation air intake At least 18 460 mm above ground or above the depth of expected snow accumulation Installation Improper installation adjustment alteration service or maintenance can cause property damage personal injury ...

Страница 5: ...um of 6 2m separation and a minimum of 18 460mm clearance above the higher of the grade or anticipated snow level CAUTION Weatherhood Clearances Wide Head Nails not supplied STRAPS AND SCREWS supplied WIDE HEAD NAILS not supplied DETAIL NOTE Front clearance of 25 inches 635 mm is recommended for servicing unit Unit is designed for horizontal installation only as shown Using full length hanger stra...

Страница 6: ...lated duct should be connected between the HRV and the supply exhaust duct system The main supply and return lines to from the HRV must be 5 inches 150mm minimum Branch lines to the individual rooms may be as small as 4 inches 100mm but 5 inch 125mm lines are preferred All ducts running through attics and unheated spaces must be sealed and insulated to code Fresh Air Ducting In applications that d...

Страница 7: ...t grille is available as part number This grille includes a removable grease filter Canadian building codes require that kitchen grilles be equipped with washable filters Field supplied balancing dampers should be installed external to the unit to balance the amount of stale air being exhausted with the amount of fresh air being brought into the house Refer to Air flow Balancing section The Round ...

Страница 8: ...ue to the differences in pressure between the HRV and the equipment it is being connected to the HRV air flow must be confirmed on site using the balancing procedure found in the installation manual Return Air 3 min recommended Weather hood arrangement requires a minimum of 6 2m separation and a minimum of 18 460mm clearance above grade or anticipated snow level CAUTION Stale air drawn from key ar...

Страница 9: ...inuously or interlocked with HRV 2 A minimum separation of 40 inches 1m is required between the two direct connections 3 The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air 4 Weather hood arrangement is for drawing purposes only Six feet 2m minimum separation required 18 inches 460mm above grade minimum or above anticipated snow level 5 Du...

Страница 10: ...n the installation manual Weather hood arrangement requires a minimum of 6 2m separation and a minimum of 18 460mm clearance above grade or anticipated snow level CAUTION Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas of house HRV must be balanced WARNING Stale Air To Outside Fresh Air From Outside STALE AIR from various parts of home i e ba...

Страница 11: ...s the dehumidistat or the fan timer should be made by a quali fied service technician Low voltage wires from the remote controls are connected to the HRV micro processor board In order to prevent electric shock when cleaning or servicing the HRV it is extremely important to confirm the polarity of the power line that is switched by the safety disconnect switch The hot line black is the proper line...

Страница 12: ...ode DIP Switch Settings The Dehumidstat Dial Main controls feature a dehumidistat dial The dehumidistat is used to reduce high winter humidity levels The dehumidis tat activates high speed ventilation when the indoor humidity level exceeds selected setting Optional Timers Timers should be present when the HRV is exhausting from specific locations i e bathrooms laundry rooms The 20 Minute Timer is ...

Страница 13: ...al Strip Red to Red Black to Black Red to Red Orange to Orange Black to Black 2040 ON OFF Dehumidistat Crank Timer Red to Red Black to Black Recirculation Control Remove factory installed jumper when installing this control Remove factory installed jumper when installing this control Factory installed jumper Circuit Board Terminal Strip Circuit Board Terminal Strip Circuit Board Terminal Strip Low...

Страница 14: ...de to provide high speed operation Changing Speeds Speed Selection Switch LOW SPEED STANDBY MED LOW SPEED Figure 1 Factory DIP Switch Settings The factory setting of the DIP switches located on the cir cuit board provides continuous low speed ventilation Optional Remote Controls will initiate high speed ventila tion Remote controls with an ON OFF switch refer to Remote Control Devices in this manu...

Страница 15: ... TPD DEFROST DETAILS P1 1 2 3 4 PIN 1 RED PIN 2 ORANGE PIN 3 BLACK PIN 4 SPARE PCB PLUG IN RED BLACK PLUG IN CONNECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only TO MOTORS BLUE RED INTERFACE RELAY CONTACTS ...

Страница 16: ...16 Wiring Diagrams Model RNC5 TPF LOW SPEED TO EXHAUST MOTOR TO SUPPLY MOTOR BLUE RED BROWN WHITE BLACK ...

Страница 17: ...Interface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y terminal is connected to the G terminal internal to the stat When R and G are closed at the furnace by dehumidistat or relay 24 Volts is sent to G at thermostat 24 Volts is then sent through Y which will initiate outdoor condenser Wire Connector Interlocking HRV Operation to an Airh...

Страница 18: ...he bottom drip pans and drains out through the bottom drain connec toions The defrost cycle repeats automatically until the air temperature rises above 27 F 3 C Defrost Operation Dehumidistat Operation HRV only Defrost Cycle DIP Switch Settings The optional HRV remote controls include a dehumidistat which controls humidity levels during the heating season The control has a selector knob with setpo...

Страница 19: ...distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube com ing out of the end of the Pitot is connected to the high pressure side of the gauge The tube coming out of the branch of the Pitot is connecte...

Страница 20: ...ired kitchens if required Placement of Pitot Tube HRV MAGNEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Low Pressure Side Magnehelic gauge Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit with magnehelic gauge Pitot tube hose and carry case NOTE Graphic is for illustrative purposes only Duct connection ports may vary ...

Страница 21: ...rilles so as not to directly spill the supply air on the occupant eg over a sofa turn down the HRV supply speed A small duct heater 1kw could be used to temper the supply air placement of furniture or closed doors is restricting themove ment of air in the home if supply air is ducted into air handler return the air handler fan may need to run continuously to distribute ventilation air com fortably...

Страница 22: ...into the top H channel approximately 1 4 6mm d with all four corners in place and the core straight and even push hard in the center of the core until the core stops on the back of the cabinet NOTE Core will appear to stick out from cabinet approxi mately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Maintenance Free 5 Drain condensate Line Clea...

Страница 23: ...23 ...

Страница 24: ......

Отзывы: