Tradewinds RNC15 Скачать руководство пользователя страница 17

17

Poor Air Flow 

Supply air feels cold

Dehumidistat is not Operating

Humidity Levels are too High in Winter 
Condensation is appearing on the 
windows

Humidity Levels are too Low 

HRV and / or Ducts Frosting up

Condensation or Ice Build Up in 
Insulated Duct to the Outside 

Water in the bottom of the HRV 

• 1/4” (6mm) mesh on the outside hoods is plugged
• filters plugged
• core obstructed
• house grilles closed or blocked
• dampers are closed if installed
• poor power supply at site
• duct is restricting HRV
• improper speed control setting
• HRV air flow improperly balanced

• poor location of supply grilles, the air flow may irritate

the occupant

• outdoor temperature extremely cold

• improper connection to ventilator
• external low voltage is shortened out by a staple or nail
• check dehumidistat setting it may be on OFF

• dehumidistat is set too high
.• lifestyle of the occupants

• moisture coming into the home from an unvented or

unheated crawl space

• moisture is remaining in the washroom/bathroom and

kitchen areas

• condensation seems to form in the spring and fall

• HRV is set at too low a speed

• dehumidistat control set too low
• blower speed of HRV is too high 
• lifestyle of occupants
• HRV air flow may be improperly balanced

• HRV air flow is improperly balanced
• malfunction of the HRV defrost system

• incomplete vapor barrier around insulated duct
• a hole or tear in outer duct covering

•  drain pans plugged
•  improper connection of HRV drain lines
•  HRV is not level
• drain lines are obstructed
•  HRV heat exchange core is not properly installed

• clean exterior hoods or vents
• remove and clean filter
• remove and clean core
• check and open grilles
• open and adjust dampers
• have electrician check supply voltage at house 
• check duct installation
• increase the speed of the HRV
• have contractor balance HRV

• locate the grilles high on the walls or under the baseboards,

install ceiling mounted diffuser or grilles so as not to directly
spill the supply air on the occupant (eg. over a sofa)

•  turn down the HRV supply speed. A small duct heater

(1kw) could be used to temper the supply air

• placement of furniture or closed doors is restricting themove-

ment of air in the home

•  if supply air is ducted into air handler return, the air handler

fan may need to run continuously to distribute ventilation air
comfortably

• check that the correct terminals have been used
• check external wiring for a short
• set the dehumidistat at the desired setting

• set dehumidistat lower
• avoid hanging clothes to dry, storing wood and venting

clothes dryer inside. Heating wood may have to be moved
outside

• vent crawl space and place a vapor barrier on the floor of the

crawl space

• ducts from the washroom/bathroom should be sized to

remove moist air as effectively as possible, use of a wash-
room/bathroom fan for short  periods will remove additional
moisture

• timer or fan can be added to washroom/bathroom exhaust
• on humid days, as the seasons change, some condensation

may appear but the home’s air quality will remain high with
some HRV use

• increase speed of the HRV

• set dehumidistat higher
• decrease HRV blower speed 
• humidity may have to be added through the use of humidi-

fiers

• have a contractor balance HRV air flow

• Note: minimal frost build-up is expected on cores before

unit initiates defrost cycle functions

• have HVAC contractor balance the HRV
• ensure working properly.

• tape and seal all joints 
• tape any holes or tears made in the outer duct covering
• ensure that the vapor barrier is completely sealed

• ensure O-Ring on drain nozzle sits properly
• look for kinks in line
• check water drain connections
• make sure water drains properly from pan

Troubleshooting

Symptom

Cause

Solution

Содержание RNC15

Страница 1: ...ains removable grease filter Heat Recovery Ventilators HRV are designed to provide fresh air while exhausting an equal amount of stale air The HRV is equipped with an aluminum core The device uses the...

Страница 2: ...min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform to CSA...

Страница 3: ...e wire min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform...

Страница 4: ...Weatherhood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weatherhood Requirements At least 6 2 m from the ventilation air intake At least...

Страница 5: ...e exhaust weatherhood At least 6 2 m away from dryer vents and air handler exhaust medium or high efficiency furnaces A minimum of at least 6 2 m from driveways oil fill pipes gas meters or garbage co...

Страница 6: ...ated duct should be connected between the HRV and the supply exhaust duct system The main supply and return lines to from the HRV must be 6 inches 150mm minimum Branch lines to the individual rooms ma...

Страница 7: ...of stale air being exhausted with the amount of fresh air being brought into the house Refer to Air flow Balancing sec tion The Round Diffuser is available in 4 100mm 5 125mm 6 150mm 8 200mm Drain Co...

Страница 8: ...e grade minimum 5 Due to the differences in pressure between the HRV and the epuipment it is being connected to the HRV s airflow must be confirmed on site using the balancing procedure found in this...

Страница 9: ...be made by a quali fied service technician Low voltage wires from the remote controls are connected to the HRV micro processor board In order to prevent electric shock when cleaning or servicing the H...

Страница 10: ...oltage Connect one per HRV only Connects to red black and orange Part No 99 116 REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern provides high speed ventilation when humidity level...

Страница 11: ...he OFF position Changing the remote control from OFF to STANDBY can be achieved by Setting the DIP Switch as per Figure 2 Figure 2 DIP Switch Settings for Standby When using a Remote Control Device th...

Страница 12: ...ECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only 12VAC P4 N C COMMON N O TO MOTOR K1 K2 K3 K4 3 4 AMP FUSE CR1 C1 VDR1 VDR2 VDR3 AUTO TRANS T9 T8 T6 T5 T4 T3 T2 P1 SPARE FAN O...

Страница 13: ...t the Interface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y termi nal is connected to the G terminal internal to the stat When R and G ar...

Страница 14: ...idity levels are in a range from 30 to 45 The dehumidistat switches the ventilator to high speed when the moisture level in the building exceeds the desired setpoint The dehumidistat switches the HRV...

Страница 15: ...istances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of...

Страница 16: ...ng Damper Field supplied Balancing Damper optional Placement of Pitot Tube HRV MAGNEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Low Pressure Side Magnehelic gauge Pitot Tube and Gauge Pitot Tube...

Страница 17: ...increase the speed of the HRV have contractor balance HRV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supp...

Страница 18: ...ops on the back of the cabinet NOTE Core will appear to stick out from cabinet approxi mately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Mainten...

Отзывы: