When using the Interface relay contacts to initiate blower operation on a fur-
nace, certain thermostats will initiate the outdoor cooling condenser when
R and G are closed.

Use this wiring configuration to prevent the Interface relay contacts from initializing
the condenser unit. This problem can occur at the thermostat because the

Y

termi-

nal is connected to the

G

terminal internal to the stat. When

R

and

G

are closed at

the furnace (by dehumidistat or relay) 24 Volts is sent to

G

at thermostat. 24 Volts is

then sent through

Y

which will initiate outdoor condenser.

 

Interlocking HRV Operation to an Airhandler/Furnace Blower

Содержание RNC15

Страница 1: ...ains removable grease filter Heat Recovery Ventilators HRV are designed to provide fresh air while exhausting an equal amount of stale air The HRV is equipped with an aluminum core The device uses the...

Страница 2: ...min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform to CSA...

Страница 3: ...e wire min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform...

Страница 4: ...Weatherhood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weatherhood Requirements At least 6 2 m from the ventilation air intake At least...

Страница 5: ...e exhaust weatherhood At least 6 2 m away from dryer vents and air handler exhaust medium or high efficiency furnaces A minimum of at least 6 2 m from driveways oil fill pipes gas meters or garbage co...

Страница 6: ...ated duct should be connected between the HRV and the supply exhaust duct system The main supply and return lines to from the HRV must be 6 inches 150mm minimum Branch lines to the individual rooms ma...

Страница 7: ...of stale air being exhausted with the amount of fresh air being brought into the house Refer to Air flow Balancing sec tion The Round Diffuser is available in 4 100mm 5 125mm 6 150mm 8 200mm Drain Co...

Страница 8: ...e grade minimum 5 Due to the differences in pressure between the HRV and the epuipment it is being connected to the HRV s airflow must be confirmed on site using the balancing procedure found in this...

Страница 9: ...be made by a quali fied service technician Low voltage wires from the remote controls are connected to the HRV micro processor board In order to prevent electric shock when cleaning or servicing the H...

Страница 10: ...oltage Connect one per HRV only Connects to red black and orange Part No 99 116 REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern provides high speed ventilation when humidity level...

Страница 11: ...he OFF position Changing the remote control from OFF to STANDBY can be achieved by Setting the DIP Switch as per Figure 2 Figure 2 DIP Switch Settings for Standby When using a Remote Control Device th...

Страница 12: ...ECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only 12VAC P4 N C COMMON N O TO MOTOR K1 K2 K3 K4 3 4 AMP FUSE CR1 C1 VDR1 VDR2 VDR3 AUTO TRANS T9 T8 T6 T5 T4 T3 T2 P1 SPARE FAN O...

Страница 13: ...t the Interface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y termi nal is connected to the G terminal internal to the stat When R and G ar...

Страница 14: ...idity levels are in a range from 30 to 45 The dehumidistat switches the ventilator to high speed when the moisture level in the building exceeds the desired setpoint The dehumidistat switches the HRV...

Страница 15: ...istances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of...

Страница 16: ...ng Damper Field supplied Balancing Damper optional Placement of Pitot Tube HRV MAGNEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Low Pressure Side Magnehelic gauge Pitot Tube and Gauge Pitot Tube...

Страница 17: ...increase the speed of the HRV have contractor balance HRV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supp...

Страница 18: ...ops on the back of the cabinet NOTE Core will appear to stick out from cabinet approxi mately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Mainten...

Отзывы: