INSTALLATION INSTRUCTION FOR HEAT RECOVERY VENTILATOR (HRV)

Package 1 of 1 contains:

1 - Assembled ventilator
1 - Bag assembly containing:

2 - Drain spout assemblies

(HRV units only)

4 - Hanging straps
1 - Installation manual

Installation Tools

tin snips

large zip ties

assorted screw drivers

fabric flexible duct

electric drill

- class

II 

rated

hammer

mastic tape

wire strippers

alum. foil duct tape

knife

zip ties

caulking gun

1/2” I.D. drain hose

smoke pencil

Balancing Tools

Pitot Tube Balancing Kit
[Case, 8 ft. vinyl tubing, Pitot tube,

magnehelic gauge (0 - 0.25”), and mounting plate]

Pitot Tube with instructions

and Digital Manometer (with resolution of
0 - 0.25” - must read to 1/100ths of an inch)

Optional Accessories

20 Minute Fan Timer

Wall Mounted Dehumidistat

Weather hood Kit

Round Diffuser

4” (100mm)
5” (125mm)
6” (150mm)
8” (200mm)

Kitchen Grille

- may be required by code for kitchen applications
- contains removable grease filter

Heat Recovery Ventilators (HRV) are designed to provide
fresh air while exhausting an equal amount of stale air.

The HRV is equipped with an aluminum core. The device
uses the stale air that is being exhausted to condition the
fresh air as it is being brought in.

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.

Shipping and Packaging List .................................................1

Required Tools ......................................................................1

Application .............................................................................1

General ..................................................................................1

Engineering Data................................................................2-3

Clearances & Requirements..................................................4

Installation ..........................................................................4-7

Installation Diagrams .............................................................8

Electrical ...............................................................................9

Optional Controls .................................................................10

Operation .............................................................................11

Wiring Diagrams ..................................................................12

Interlocking HRV to Furnace ...............................................13

Air Flow Balancing..........................................................15-16

Troubleshooting ...................................................................17

Maintenance .......................................................................18

Shipping and Packing List

Application

General

Table of Contents

Required Tools

* LEAVE FOR HOMEOWNER

NOTE: Due to ongoing research and product development, specifications,

ratings and dimensions are subject to change without notice.

TW-25

1206

TM

HEAT RECOVERY VENTILATOR

HEAT RECOVERY VENTILATOR

MODELS RNC15/RNC25

Содержание RNC15

Страница 1: ...ains removable grease filter Heat Recovery Ventilators HRV are designed to provide fresh air while exhausting an equal amount of stale air The HRV is equipped with an aluminum core The device uses the...

Страница 2: ...min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform to CSA...

Страница 3: ...e wire min 100 length max 99 186 Weather Hoods 2 6 150mm c w 1 4 6mm screen 99 116 Dehumidistat Ventilation Control Dehumidistat with ON OFF 99 130 Dehumidistat Control Dehumidistat All units conform...

Страница 4: ...Weatherhood Location and Installation Weatherhood kit includes two fixed cover hoods with a 1 4 6mm mesh screen Exhaust Weatherhood Requirements At least 6 2 m from the ventilation air intake At least...

Страница 5: ...e exhaust weatherhood At least 6 2 m away from dryer vents and air handler exhaust medium or high efficiency furnaces A minimum of at least 6 2 m from driveways oil fill pipes gas meters or garbage co...

Страница 6: ...ated duct should be connected between the HRV and the supply exhaust duct system The main supply and return lines to from the HRV must be 6 inches 150mm minimum Branch lines to the individual rooms ma...

Страница 7: ...of stale air being exhausted with the amount of fresh air being brought into the house Refer to Air flow Balancing sec tion The Round Diffuser is available in 4 100mm 5 125mm 6 150mm 8 200mm Drain Co...

Страница 8: ...e grade minimum 5 Due to the differences in pressure between the HRV and the epuipment it is being connected to the HRV s airflow must be confirmed on site using the balancing procedure found in this...

Страница 9: ...be made by a quali fied service technician Low voltage wires from the remote controls are connected to the HRV micro processor board In order to prevent electric shock when cleaning or servicing the H...

Страница 10: ...oltage Connect one per HRV only Connects to red black and orange Part No 99 116 REMOTE DEHUMIDISTAT requires 2 wires anywhere humidity is a concern provides high speed ventilation when humidity level...

Страница 11: ...he OFF position Changing the remote control from OFF to STANDBY can be achieved by Setting the DIP Switch as per Figure 2 Figure 2 DIP Switch Settings for Standby When using a Remote Control Device th...

Страница 12: ...ECTOR BI DIRECTIONAL DAMPER MOTOR ORANGE RED BLACK ORANGE Model RNC5 Only 12VAC P4 N C COMMON N O TO MOTOR K1 K2 K3 K4 3 4 AMP FUSE CR1 C1 VDR1 VDR2 VDR3 AUTO TRANS T9 T8 T6 T5 T4 T3 T2 P1 SPARE FAN O...

Страница 13: ...t the Interface relay contacts from initializing the condenser unit This problem can occur at the thermostat because the Y termi nal is connected to the G terminal internal to the stat When R and G ar...

Страница 14: ...idity levels are in a range from 30 to 45 The dehumidistat switches the ventilator to high speed when the moisture level in the building exceeds the desired setpoint The dehumidistat switches the HRV...

Страница 15: ...istances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0 25 in 0 62 Pa of...

Страница 16: ...ng Damper Field supplied Balancing Damper optional Placement of Pitot Tube HRV MAGNEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Low Pressure Side Magnehelic gauge Pitot Tube and Gauge Pitot Tube...

Страница 17: ...increase the speed of the HRV have contractor balance HRV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supp...

Страница 18: ...ops on the back of the cabinet NOTE Core will appear to stick out from cabinet approxi mately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Mainten...