6.3.4.3 Function control (PNU 65004)
Via the function control, measuring system-related functions can be enabled or disabled independently
of each other, the code sequence can be set and the encoder type read out.
PNU
65004
Meaning
Function control
Data type
Unsigned32
Access
read/write
Activation
PNU 972
Save
PNU 971
Bits
Definition
0
Code Sequence
, see chap. 6.3.3.9 on page 121
0: rising position values, when the magnet is moved to the end of the bar
1: falling position values, when the magnet is moved to the end of the bar
1
Encoder Class 4 functionality
, see chap. 6.3.3.10 on page 122
0: disabled
1: enabled
2
Preset affects XIST1
, see chap. 6.3.3.11 on page 122
0: enabled
1: disabled
3
Scaling function control
, see chap. 6.3.3.12 on page 122
0: disabled
1: enabled
4
Alarm channel control
, see chap. 6.3.3.13 on page 123
0: disabled
1: enabled
5
Compatibility Mode V3.1
, see chap. 6.3.3.14 on page 123
0: enabled
1: disabled
6
Encoder type
, also see chap. 6.3.4.2.2 on page 133
0: Rotary encoder, resolution in steps per revolution
1: Linear encoder, resolution in nm per step
7 - 31
reserved