11.5 Other faults
Fault
Cause
Remedy
Position skips
of the measuring
system
Strong vibrations
Vibrations, impacts and shocks, e.g. on presses, are
dampened with "shock modules". If the error recurs
despite these measures, the measuring system must be
replaced.
Electrical faults
EMC
Use cables with twisted pair wires for data and supply.
Shielding and wire routing must be performed according to
the respective field-bus system construction guidelines.