Parameterization
TR-Electronic GmbH 2013, All Rights Reserved
Printed in the Federal Republic of Germany
Page 156 of 171
TR - ECE - BA - DGB - 0102 - 03
09/23/2014
8.7.3.5 Attribute 5, Interface Configuration
The
Interface Configuration
attribute contains the configuration parameters
required to operate the measuring system as a TCP/IP node. In order to prevent
incomplete or incompatible configuration, the parameters making up the Interface
Configuration attribute cannot be set individually. To modify the Interface
Configuration attribute, the user should first Get the
Interface Configuration
Attribute
, change the desired parameters then set the attribute.
Name
Description
IP address
Sets the
device’s IP address
Network mask
Sets the
device’s Subnet mask
Gateway address
Sets the device’s default Gateway
Name server
0, not supported
Name server 2
0, not supported
Domain name
0, not supported
8.7.3.5.1 Obtaining the IP parameter
In the start-up phase of the measuring system the stored configuration from attribute
5, the stored value from attribute 3
Configuration Control
(page 155) and the
value of the hardware switches (page 104) is read and is evaluated as follows:
Config. Control
Switch
Action
Description
0x00
0x00
FLASH active
Configuration is obtained from the FLASH.
0x00
0x00 … 0xFE
Switch active
IP address: 192.168.1.<Switch position>
Subnet mask: 255.255.255.0
Default Gateway: 192.168.1.254
0x00
0xFF
DHCP request
Configuration is obtained from a DHCP
server. The DHCP requests are only
stopped if a response was received.
0x02
0x00
other
-
none
Prohibited!
Request is answered with error code 0x20.