9.2.9 Over voltage or too low voltage protection diagnosis and solution(P1)

   

 

 

Содержание TPG A128 IVP

Страница 1: ...Service Manual MODEL TPN A128 IVP TPG A128 IVP TPN A135 IVP TPG A135 IVP TPN A180 IVP TPG A180 IVP TPN A240 IVP TPG A240 IVP...

Страница 2: ...Pipe length and the elevation 15 6 4 Installation for the first time 16 6 5 Adding the refrigerant after running the system for many years 19 6 6 Re installation while the indoor unit need to be repa...

Страница 3: ...mble or repair the product there is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is ri...

Страница 4: ...y plug during operation There is risk of fire or electric shock Do not touch operation the product with wet hands Do not place a heater or other appliance near the power cable There is risk of fire an...

Страница 5: ...er supply plug or turn off the breaker There is risk of product damage or failure or unintended operation Take care to ensure that nobody could step on or fall onto the outdoor unit This could result...

Страница 6: ...or units Always insert the filter securely Clean the filter every two weeks or more often if necessary A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction...

Страница 7: ...VP 24k TPN A240 IVP TPG A240 IVP Filter Ionizer O Silver Ico Filter O Vitamin C Filter O 3M HAM Filter O Bio Filter O Golden Fin O Killer of Formaldehyde Compressor Crankcase Heater O Self Clean O Fol...

Страница 8: ...mm Dimension of installation hole mm TPG A128 IVP 111 5 100 45 65 TPG A135 IVP 83 5 100 45 TPG A180 IVP 207 150 45 TPG A240 IVP 139 100 45 Model W D H TPN A128 IVP 710 189 250 TPN A135 IVP 790 196 27...

Страница 9: ...More than 70cm More than 30cm More than 60cm Service space Fence or obstacles Model W D H W1 A B TPG A128 IVP 780 250 540 843 549 276 TPG A135 IVP 780 250 540 843 549 276 TPG A180 IVP 760 285 590 823...

Страница 10: ...INDOOR OUTDOOR LIQUID SIDE GAS SIDE HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR 2 WAY VALVE 3 WAY VALVE CHECK VALVE Heating Model only CAPILIARY TUBE REVERSING VALVE Heating Model onl...

Страница 11: ...11 5 Wiring Diagram 5 1 Indoor Unit TPN A128 IVP TPN A135 IVP TPN A180 IVP TPN A240 IVP...

Страница 12: ...12 5 2 Outdoor Unit TPGA128IVP TPG A135 IVP TPG A180 IVP...

Страница 13: ...13 TPG A240 IVP...

Страница 14: ...4 6500 663kgf cm 6700 683kgf cm 6 2 Connecting the cables The power cord of connect should be selected according to the following specifications sheet Rated current of appliance Nominal cross section...

Страница 15: ...id TPN A128 IVP TPG A128 IVP 3 8 9 52 1 4 6 35 5 8 20 20 TPN A135 IVP TPG A135 IVP 5 8 20 20 TPN A180 IVP TPG A180 IVP 1 2 12 7 1 4 6 35 5 10 25 20 TPN A240 IVP TPG A240 IVP 5 8 15 9 3 8 9 52 5 10 25...

Страница 16: ...t brush to check for leakage of the connecting points of the piping If bubbles come out the pipes have leakage 1 Air purging with vacuum pump 1 Completely tighten the flare nuts of the indoor and outd...

Страница 17: ...indicator is a little higher than the atmosphere pressure Then remove the charge hose from the 3 way valve 8 Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve...

Страница 18: ...rant if the pipe length 5m Procedure 1 Connect the charge hose to the charging cylinder open the 2 way valve and the 3 way valve Connect the charge hose which you disconnected from the vacuum pump to...

Страница 19: ...nnect the charge hose to the 3 way service port open the 2 way valve and the 3 way valve Connect the charge hose to the valve at the bottom of the cylinder If the refrigerant is R410A make the cylinde...

Страница 20: ...e the indoor unit need to be repaired 1 Collecting the refrigerant into the outdoor unit Procedure 1 Confirm that both the 2 way and 3 way valves are set to the opened position Remove the valve stem c...

Страница 21: ...y the refrigerant Procedure 1 Confirm that both the 2 way and 3 way valves are set to the closed position 2 Connect the charge set and a charging cylinder to the service port of the 3 way valve Leave...

Страница 22: ...tighten the service port cap to a torque 18N m Be sure to check the gas leakage 6 7 Re installation while the outdoor unit need to be repaired 1 Evacuation for the whole system Procedure 1 Confirm th...

Страница 23: ...on the charge set and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant or can be charged with a little at a time approximately 150g eac...

Страница 24: ...e above conditions certain safety protection features may come into operation and cause the unit to operate abnormally 2 The room relative humidity should be less than 80 If the air conditioner operat...

Страница 25: ...anation on indoor display board Auto indicator This indicator illuminates when the air conditioner is in AUTO operation PRE DEF Indicator This indicator illuminates when the air conditioner starts def...

Страница 26: ...When Indoor Fan Speed keeps too low 300RPM for certain time the unit will stop and the LED will display the failure 8 3 5 Inverter module protection The Inverter module has a protection function abou...

Страница 27: ...void the case that the air conditioner is in urgent need Fault temp sensor Operation in cooling drying and fan only mode Operation in heating mode T1 Run supposed T1 26 high fan speed Run supposed T1...

Страница 28: ...emp T2 of the compressor just starts running as Tcool In the beginning 5 minutes after the compressor starts up if T2 Tcool 2 does not keep continuous 4 seconds and this situation happens 3 times the...

Страница 29: ...g function is disabled and no setting temperature is displayed 3 Indoor fan can be set to high med low auto 4 The louver operates same as in cooling mode 5 Auto fan For TPN A240 IVP 27 5 27 High Low 2...

Страница 30: ...T4FREMAX6 Fmax T4FREMAX7 Meanwhile the maximum frequency is limited by the indoor fan speed Indoor fan speed Maximum frequency High speed turbo function No limit Silent mode Fixed at F3 If users swit...

Страница 31: ...he frequency to 3 grade higher until to FREMAX B E Increase the frequency to 2 grade higher until to FREMAX F G Increase the frequency to 1 grade higher until to FREMAX H Keep the current frequency I...

Страница 32: ...ooling While A B C means different fan speed of outdoor unit 8 4 2 3 Indoor fan running rules In cooling mode indoor fan runs all the time and the speed can be selected as high medium low auto and sil...

Страница 33: ...runs at F1 If T3 54 the compressor will keep running at the current frequency T3 52 the compressor will not limit the frequency and resume to the former frequency T3 60 for 5 seconds the compressor wi...

Страница 34: ...its to the following rule Fmax T4FREHEATMAX1 34 T4 Off 33 28 27 25 24 22 21 19 18 16 17 15 14 12 11 6 5 Fmax T4FREHEATMAX2 Fmax T4FREHEATMAX3 Fmax T4FREHEATMAX4 Fmax T4FREHEATMAX5 Fmax T4FREHEATMAX6 F...

Страница 35: ...the compressor running frequency will be controlled as below 5 0 4 5 3 5 3 0 2 5 2 0 1 5 T1 Ts T 1 0 I G F E D C B A 0 5 4 0 H J While the zones of A B C are corresponding to different compressor runn...

Страница 36: ...rules 21 19 A C 18 16 D 15 13 12 10 B E Heating 8 4 3 3 Indoor fan running rules In heating mode indoor fan can be selected as high medium low auto and silent The anti cold wind function is preferent...

Страница 37: ...be forced to run 127 seconds with breeze During this period the anti cold wind is disabled Auto fan action in heating mode For 240 IVP 2 5 T1 Ts 2 0 High Low 1 0 Medium 1 5 For other models 1 0 2 0 3...

Страница 38: ...0 2 If the compressor cumulate running time is up to 35 minutes and T3 TCDI2 T3 T30SUBT3TWO T30 3 If the compressor cumulate running time is up to 29 minutes and T3 TCDI3 for 3 minutes 4 If the compre...

Страница 39: ...utdoor fan Indoor fan Indoor fan breeze 10s xx 10s no longer than 10m 30s FrequencyF16 10s Frequency F3 xx 60 For TPN A180 IVP TPG A180 IVP TPN A240 IVP TPG A240 IVP Compressor on off on on on off off...

Страница 40: ...will choose cooling heating or fan only mode according to T T T1 Ts T T1 Ts Running mode T 1 Cooling 1 T 1 Fan only T 1 Heating Indoor fan will run at auto fan of the relevant mode The louver operate...

Страница 41: ...hen the machine is off pressing the touch button will carry the machine to forced auto mode If pressing the button once again within 5 seconds the machine will turn into forced cooling mode In forced...

Страница 42: ...e setting temperature rises 1 be lower than 30 every one hour 2 hours later the setting temperature stops rising and indoor fan is fixed as low speed When heating the setting temperature decreases 1 b...

Страница 43: ...nditions the compressor will have 3 minutes delay when restarts 8 4 10 8 Heating optional In heating operation the preset temperature of the air conditioner can be as lower as 8 which keeps the room t...

Страница 44: ...circuit of evaporator coil temperature T2 sensor 7 times X EC Refrigerant Leakage Detection 2 times O F1 Open circuit or short circuit of outdoor ambient T4 temperature sensor 3 times O F2 Open circui...

Страница 45: ...45 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution E0 EEPROM a read only memory whose contents can be erased and reprogrammed using a pulsed voltage...

Страница 46: ...46 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1...

Страница 47: ...47 9 2 3 Zero crossing detection error diagnosis and solution E2 9 2 4 Indoor fan speed has been out of control diagnosis and solution E3...

Страница 48: ...48 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...

Страница 49: ...Does the problem remain again No Is there any leakage Especially the connection parts such as the gas valve and the liquid valve No Shut off the power supply and turn it on 5 seconds later Is it still...

Страница 50: ...50 9 2 7 Outdoor fan speed has been out of control diagnosis and solution F5...

Страница 51: ...51 9 2 8 IPM malfunction or IGBT over strong current protection diagnosis and solution P0...

Страница 52: ...52 9 2 9 Over voltage or too low voltage protection diagnosis and solution P1...

Страница 53: ...53 9 2 10 Inverter compressor drive error diagnosis and solution P4...

Страница 54: ...TAGE CAUTION Connect discharge resistance approx 100 40W or soldering iron plug between terminals of the electrolytic capacitor on the contrary side of the outdoor PCB Note The picture above is only f...

Страница 55: ...of each winding by using the multi meter Table 1 Some frequently used R T data for T1 T2 T3 and T4 sensor Temperature 5 10 15 20 25 30 40 50 60 Resistance Value K 26 9 20 7 16 1 12 6 10 8 5 2 3 5 2 4...