22
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
6.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for
the whole system
Procedure:
1).
Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
Содержание TPG A128 IVP
Страница 11: ...11 5 Wiring Diagram 5 1 Indoor Unit TPN A128 IVP TPN A135 IVP TPN A180 IVP TPN A240 IVP...
Страница 12: ...12 5 2 Outdoor Unit TPGA128IVP TPG A135 IVP TPG A180 IVP...
Страница 13: ...13 TPG A240 IVP...
Страница 46: ...46 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1...
Страница 48: ...48 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 50: ...50 9 2 7 Outdoor fan speed has been out of control diagnosis and solution F5...
Страница 51: ...51 9 2 8 IPM malfunction or IGBT over strong current protection diagnosis and solution P0...
Страница 52: ...52 9 2 9 Over voltage or too low voltage protection diagnosis and solution P1...
Страница 53: ...53 9 2 10 Inverter compressor drive error diagnosis and solution P4...