9. FUNCTION

1. Cooling operation

Room temperature setting range is 61 ~ 90˚F (16 ~ 32˚C).
Room temperature indication range is 32 ~ 122˚F (0 ~ 50˚C).
State of operating is as shown below.

A. When the room temperature is 2˚F (1˚C) higher than the setting temperature, the compressor operates at

least for 150 seconds.
If the room temperature drops 2˚F (1˚C) lower than the setting temperature, the compressor stops.

B. For protection of the compressor, it will not restart at least for 150 seconds after it has stopped.

C. In the condition that the Setting tempe2˚F (+1˚C) > Room temperature > Setting temperature -2˚F

(–1˚C), the compressor operates for more than 150 seconds.
If the room temperature drops more than 2˚F (1˚C) from the setting temperature, the compressor stops.

D. When the room temperature is 2˚F (1˚C) lower than the setting temperature, the compressor will not start.

E. The fan will operate at the selected fan speed.

2. Dehumidifying operation

When the room temperature is lower than 77˚F (25˚C) (setting temperature), the unit enters in the dehumidifying
operation.
Changes in the dehumidifying control

More than

150 seconds

+2˚F (+1.0˚C)

Room

temperature

Setting

temperature

-2˚F (-1.0˚C)

Compressor

Fan speed

ON

Selected

fan speed

ON

Selected

fan speed

OFF

Selected

fan speed

ON

Selected

fan speed

OFF

Selected

fan speed

More than

150 seconds

OFF

Selected

fan speed

77˚F (25˚C)

72˚F (22˚C)

66˚F (19˚C)

Selected

fan speed

Room

temperature

Low

Low

Low

A: Dry

79˚F (26˚C)
Cool mode ON

Cold wind

B: Dry

C: Dry

Содержание TAD-30F

Страница 1: ...SERVICE MANUAL MODEL TAD 30F ...

Страница 2: ... at bedtime Venting is not required However if the unit is to be used exclusively in one space the cooling efficiency will be enhanced by using the venting kit accessory 2 OPERATIONAL FEATURES 1 COOLING OPERATION Normally cool air is directed out the front louvers by the circulation fan which has three 3 stages of fan speed 2 AUTOMATIC OPERATION Once the desired function has been set it is memoriz...

Страница 3: ... HAF air filter inside Air intake grille Pre filter Air intake Evaporator Exhaust outlet Air intake Condenser Power supply cord Caster Horizontal louver Carrying handle Operation panel Air outlet Vertical louver Front panel Drain water outlet LCDI plug ...

Страница 4: ...om Temp emp Room Temp Digital indicator Adjust buttons Timer button Signal receptor Fan speed button Mode button Power button Tank full lamp Fan mode lamp Dry mode lamp Cool mode lamp Room temp lamp Set temp lamp Timer set lamp Digital indicator Power button Adjust button Fan speed button C F toggle button Adjust button Mode button Timer button 4 NAME AND FUNCTIONS OF OPERATIONAL PANEL ...

Страница 5: ...kind DO NOT attempt to shorten or alter power cord in any way DO NOT apply any excessive force or pressure to the power supply cord Make sure that the plug is free of dust DO NOT use an extension cord DO NOT turn on and off by inserting or removing the plug which may cause electric shock or fire If there is a fear of lightning stop the unit and disconnect the power supply cord DO NOT touch the eva...

Страница 6: ...E MODEL OUTPUT POWER OPERATING CYCLE MODEL OUTPUT POWER UNIT in FT2 V Hz V B T U GAL H A W CFM W uF V A W uF V W uF V W mm R22 lbs F lbs TAD 30F 18 5 8 W 13 9 16 D 34 1 4 H 472 W 345 D 869 H mm 140 200 13 19m2 115 60 198 264 10 000 0 48 1 8 L H 9 0 950 188 320 m3 hr 2R12S3R126A 6A 740 35 250 RU 3505250 18 0 LS 13T3 4P 55 4 250 LS 40T1 4P 85 6 450 WT 15T1 01 12 2 6 O D 1 6 I D 950 L 3R13S17FPI 3R14...

Страница 7: ...ar panel No 20 remove the rear panel 4 Remove three 3 screws each from the back and one 1 screw each from the side bottom of right left side panels No 22 and No 23 total eight 8 screws 5 Remove the operation panel form the top plate No 19 Since it is locked with the claw at the top lift it upward to remove Caution Separate at the plastics section with care not to damage the PCB 6 Remove three 3 sc...

Страница 8: ...tes violently There is a power failure The plug is not connected The timer is unable to work The main switch has not been pressed The set temperature is too close to the room s temperature There is something blocking the suction vent on the back of condenser The fan on the condenser is blocked Malfunction There is a window opened There is a source of heat operating in the room burner lamp etc or t...

Страница 9: ...n 150 seconds If the room temperature drops more than 2 F 1 C from the setting temperature the compressor stops D When the room temperature is 2 F 1 C lower than the setting temperature the compressor will not start E The fan will operate at the selected fan speed 2 Dehumidifying operation When the room temperature is lower than 77 F 25 C setting temperature the unit enters in the dehumidifying op...

Страница 10: ...More than 79 F 26 C A 77 F 73 F 25 C 23 C B 72 F 68 F 22 C 20 C C Less than 66 F 19 C Compressor ON 9min 3min 9min 3min 6min 3min Selected fan speed Low Low Low J01 J03 SENSOR J02 MICROS W J01 J02 LINE RED RED RED RED RED BLUE BLUE BLUE BLUE WATER MOTOR L N WHITE BLUE BLUE COMP T01 NATURE 120V 60Hz WHITE BLUE WHITE BLUE WHITE COMPRESSOR CAPACITOR CAPACITOR CAPACITOR OUTDOOR MOTOR INDOOR MOTOR ...

Страница 11: ... 22740203 Capacitor B Main circuit board Capacitor C Indication lamp circuit Front panel Power supply cord Top plate Rear panel Intake air grille Right side panel Left side panel HAF Filter NO 25 26 27 28 29 30 31 32 33 34 PART 22740240 22740249 22740250 22740254 22740253 22740252 22740281 22740276 22740295 22740299 Charcoal filter Exhaust duct hose Exhaust duct connector Exhaust duct hose adapter...

Страница 12: ...TOYOTOMI CO LTD 5 17 Momozono cho Mizuho ku Nagoya 467 0855 Japan www toyotomi jp New 5 05 Printed in Japan ...

Отзывы: