Troubleshooting
46
Electrical Control
2.2. Self-diagnosis
,QGRRUXQLW¶V/('LQGLFDWLRQ
(1) For the Big Four-way cassette & the A5 Duct
During malfunction or protection, the indicators and digital LED displays as follow:
No
Operation
Timer
Def/Fan
Alarm
Digital LED Display
Malfunction or protection
1
X
ƿ
X
X
E2
Indoor temperature sensor is abnormal
2
ƿ
X
X
X
E3
Evaporator temperature sensor is abnormal
3
X
X
ƿ
X
E4
Condenser temperature sensor is abnormal
4
ƿ
ƿ
X
X
E7
EEPROM malfunction
5
X
X
X
ƿ
E8
Full-water malfunction
Note:
³
X
´
means off,
³
ƿ
´
means flashes at 5Hz
(2) For the other types indoor unit
No
Operation
Timer
Def/Fan
Alarm
Information
Remark
1
ƾ
X
X
X
Normal standby
Nothing wrong with the unit
when LED indicate these
contents.
2
X
X
X
X
Normal off
3
Ȗ
X
X
X
Normal running
4
ƿ
X
Ȗ
X
Forced cooling
5
X
ƿ
X
X
Indoor temperature sensor is
abnormal
Recover automatically after
errors are eliminated (For T3
PDOIXQ3FDQ¶W
recover automatically)
6
ƿ
X
X
X
Evaporator temperature sensor is
abnormal
7
X
X
ƿ
X
Condenser temperature sensor is
abnormal
8
ƿ
ƿ
X
X
EEPROM malfunction
9
X
X
X
ƿ
Full-water malfunction
Note:
³
Ȗ
´
means on ,
³
X
´
means off,
³
ƿ
´
means flashes at 5Hz,
³
ƾ
´
means flashes at 0.5Hz
Содержание CFT100A-R
Страница 1: ...Service Manual MODEL CFT35A R CFT50A R CFT70A R CFT100A R CFT140A R CFT170A R ...
Страница 2: ......
Страница 4: ...Service Space 6 Ceiling Floor Type 3 Service Space ...
Страница 5: ...Wiring Diagrams Ceiling Floor Type 7 4 Wiring Diagrams CFT 35A Ri CFT 50A Ri ...
Страница 6: ...Wiring Diagrams 8 Ceiling Floor Type CFT 70A Ri ...
Страница 7: ...Wiring Diagrams Ceiling Floor Type 9 CFT 100A Ri ...
Страница 8: ...Wiring Diagrams 10 Ceiling Floor Type CFT 140A Ri CFT 170A Ri ...
Страница 22: ...Wiring Diagrams Outdoor Units 27 4 Wiring Diagrams CFT 35A Ro ...
Страница 23: ...Wiring Diagrams 28 Outdoor Units CFT 50A Ro CFT 70A Ro ...
Страница 24: ...Wiring Diagrams Outdoor Units 29 CFT 100A Ro ...
Страница 25: ...Wiring Diagrams CFT 140A Ro CFT 170A Ro 30 Outdoor Units ...