Electrical Control Function
Electrical Control
41
For the others type::
The compressor is running, and 4-way valve and outdoor fan stop. The indoor fan works as anti-cold wind
procedure. When defrosting is over, the compressor keeps running and the 4-way valve and outdoor fan will
start up.
For 3-phase outdoor units:
z
Condition of defrosting:
T3<0
đ
and the compressor keeps running over 45 minutes. Meanwhile T3
ψ
-3
đ
for 3minutes.
z
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal
heating mode.
A: T3 rises to be higher than 20
ć
.
B: The machine has run for 10 minutes in defrosting.
z
Defrosting action
φ
The compressor is running, and 4-way valve and outdoor fan stop. The indoor fan works as anti-cold wind
procedure. When defrosting is over, the compressor keeps running and the 4-way valve and outdoor fan will
start up.
Setting defrosting time
45S 45S
Compressor
4 way valve 40S
40S
Outdoor fan
Indoor fan
10S
Содержание CFT100A-R
Страница 1: ...Service Manual MODEL CFT35A R CFT50A R CFT70A R CFT100A R CFT140A R CFT170A R ...
Страница 2: ......
Страница 4: ...Service Space 6 Ceiling Floor Type 3 Service Space ...
Страница 5: ...Wiring Diagrams Ceiling Floor Type 7 4 Wiring Diagrams CFT 35A Ri CFT 50A Ri ...
Страница 6: ...Wiring Diagrams 8 Ceiling Floor Type CFT 70A Ri ...
Страница 7: ...Wiring Diagrams Ceiling Floor Type 9 CFT 100A Ri ...
Страница 8: ...Wiring Diagrams 10 Ceiling Floor Type CFT 140A Ri CFT 170A Ri ...
Страница 22: ...Wiring Diagrams Outdoor Units 27 4 Wiring Diagrams CFT 35A Ro ...
Страница 23: ...Wiring Diagrams 28 Outdoor Units CFT 50A Ro CFT 70A Ro ...
Страница 24: ...Wiring Diagrams Outdoor Units 29 CFT 100A Ro ...
Страница 25: ...Wiring Diagrams CFT 140A Ro CFT 170A Ro 30 Outdoor Units ...