![Town & Country Fireplaces TC36.NG02CN Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/town-and-country-fireplaces/tc36-ng02cn/tc36-ng02cn_instructions-manual_1141094010.webp)
TC36.NG02CN 210411-16
10
1.
Remove the plug from the
pressure test port using a 3/16” hex
head wrench. The plug is located
between the right side lintel and
fi rebox side. (Fig. #14)
2.
Thread the extension test fi tting into the
open test port. (Fig. #15)
3.
Attach a pressure gauge onto the
fi tting.
4.
When testing is complete remove the
extension test fi tting and replace the plug.
Thread sealant will be required to ensure
a gas tight connection.
Correct gas pressure requirement:
Supply Pressure
Natural Gas
(For purpose of input adjustment)
Minimum
5.0"
WC
Maximum 13.9"
WC
Manifold
Pressure
Maximum
3.8"
WC
Minimum
2.1"
WC
Note: To test the gas pressure, turn off the
gas supply before removing the plug from
the supply pressure test port or manifold
pressure test port.
Verify gas pressures with the fi replace lit
and on the highest setting.
Fig #14
Fig #15
Gas Pressure Check
SUPPLY
PRESSURE
MANIFOLD
PRESSURE
Fig #16