7
a t o t a l v i e w o f f i r e
1.3.5
Chimney flue floor duct
In the case of concrete floors
, an opening must be provided when concreting for any floor ducts, leaving
around the flue sufficient space for putting in place a fire break plate.
No joint between the flue elements must be located in the thickness of the floor.
Wooden floor or false ceiling
, it is advisable to use parts supplied by the flue manufacturer in order to
observe the associated precautions: stability, safety distance, thermal shock and free expansion of the flue.
The fitting of perforated safety distance plates is compulsory (case of a metal flue).
1.3.6
Safety distance of the chimney flue
The safety distances to be observed for the chimney flue are those of CSTB (Scientific and Technical
Centre for Building) graphs and DTU (Building Code) standards.
1.3.7
Covering flues
The temperature of the outside wall of the chimney flue must not exceed 50°C
(living areas) or 80°C (non living areas or inaccessible areas). If this is not the
case, the flue must be covered or concealed in casing or housing.
If the flue is insulated, ensure that you place the aluminium part of the insulant
against the flue. Secure with non-flammable adhesive foil tape.
1
2
3
1
– Flue
2- Wood
3- Safety distance
Covered flue