Step 4 — Space Temperature Averaging — 

Ap-

plications that require averaging using multiple remote space 
temperature sensors can be satisfied using either 4 or 9 sensors 
as shown in Fig. 25. For single space temperature sensor wir-
ing, refer to the base unit installation instructions. Temperature 
sensor calibration can be checked by measuring actual resis-
tance at a temperature with an ohmmeter and comparing to the 
values listed in Table 2.

NOTE: Only Totaline® sensors (P/N P274-0401) may be 
used for standard space temperature sensor averaging. Sen-
sors must be used singly or in multiples of 4 and 9, with 
total sensor wiring not to exceed 1000 feet.

Step 5 — Set Thermostat Configuration — 

Configuration options, like DIP switch settings, are intended to 
be selected at installation and are not normally modified by the 
homeowner. These options are not discussed in the corre-
sponding owner’s manual and must be done as part of the 
installation. A special procedure for the thermostat allows 
entry into the Configuration mode. To enter Configuration 

mode, press and hold the Fan button for approximately 10 sec-
onds. The room temperature display will disappear and the 
option number (smaller) will be displayed in the upper right 
corner on the thermostat display. The option number will be 
flashing and can be changed with the Up and Down Arrow 
buttons. Once the desired configuration option is displayed, 
press the Set Time/Temp button to configure the option. See 
Table 3. The option number will stop flashing and the configu-
ration value (larger) on the left of the thermostat display will 
flash. Change the configuration value with the Up and Down 
Arrow buttons. Press the Set Time/Temp button again to save 
the configuration and change a different configuration. Record 
all chosen configuration options on page 16. Press the End but-
ton to exit Configuration mode. The thermostat will automati-
cally exit Configuration mode if no button is pressed for 3 
minutes.
NOTE: When setting the configuration on the thermostat, 
the configuration “on” is displayed as On, and the configu-
ration “off” is displayed as OF.

Table 2 — Temperature Sensor Resistance vs. Temperature Values

Table 3 — Thermostat Configuration Options

 

 TEMPERATURE

OHMS

 TEMPERATURE

OHMS

F

C

F

C

30

–1

34,480

  76

24

10,250

32

  0

32,630

  78

26

  9,750

34

  1

30,760

  80

27

  9,300

36

  2

29,220

  82

28

  8,840

38

  3

27,470

  84

29

  8,432

40

  4

26,020

  86

30

  8,042

42

  6

24,680

  88

31

  7,668

44

  7

23,320

  90

32

  7,310

46

  8

22,070

  92

33

  6,993

48

  9

20,910

  94

34

  6,661

50

10

19,830

  96

36

  6,368

52

11

18,820

  98

37

  6,085

54

12

17,870

100

38

  5,811

56

13

16,920

102

39

  5,571

58

14

16,160

104

40

  5,313

60

16

15,260

106

41

  5,088

62

17

14,530

108

42

  4,869

64

18

13,790

110

43

  4,660

66

19

13,090

112

44

  4,450

68

20

12,480

114

46

  4,268

70

21

11,860

116

47

  4,091

72

22

11,270

118

48

  3,918

74

23

10,750

120

49

  3,750

OPTION NO.

DESCRIPTION

CONFIGURATION 

VALUE RANGE

DEFAULT

01

Anticipator adjustment

1 to 9

3

02

Clean filter timer adjustment

OF, 1 to 9

2

03

Fahrenheit or Celsius operation

F, C

F

04

Enable Fan (G) On with any heat (W)

OF, On

On (enabled)

05-07

N/A

08

Auxiliary Heat Lockout Temperature

OF, 5 to 55 F

OF

09-12

N/A

13

Room temperature offset adjustment

-5 to 5 F

0 F (no offset)

14

N/A

15

Enable AUTO mode

OF, On

On (enabled)

Содержание Gold P274-1100

Страница 1: ...evere personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL Totaline 7 day programmablethermostatsarewall mount ed low voltage thermostats which maintain room temperature by controlling the operation of an HVAC heating ventilation and air...

Страница 2: ...default ON Normal recovery HP AC SELECT SWITCH C Active on 1200 and 1300 Models Only Use Switch C to select between AC and HP installations The 1200 and 1300 models have an extra relay to control the HP reversing valve When a 1200 model thermostat is placed in AC mode this extra relay is converted to a second stage heat output This allows thermostat control of 2 stage fur naces or 2 stage strip he...

Страница 3: ... pump HS Intelligent heat staging with a variable speed fan coil and 1 speed heat pump Table 1 Model No and Proper Wiring for Intended Applications LEGEND Terminals S2 and C are internally connected Do not ground shield to terminal C of thermostat Be careful not to drill into wiring in the wall Electrical shock could result Improper wiring or installation may cause damage to the thermostat Check t...

Страница 4: ...W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODEL 1100 THERMOSTAT TWO STAGE OR VARIABLE SPEED FURNACE SINGLE SPEED AIR CONDITIONER W W1 Y Y2 HUM W2 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 1 and 6 on page 9 24 VAC HOT FAN COOL STAGE 1 HEAT STAGE 1 N A N A R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODE...

Страница 5: ... Y Y2 O W2 B S1 S2 MODEL 1100 THERMOSTAT SPLICE BOX GRN WHT BRN WHT BRN C Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION HEATER CONTROL BOX RED YEL SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 1 9 and 10 on page 9 24 VAC HOT FAN HEAT STAGE 1 COOL STAGE 1 HEAT STAGE 2 N A R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODEL 1200 THERMOS...

Страница 6: ... N A R G R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C C MODEL 1200 THERMOSTAT EASY SELECT TERMINAL BOARD J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING SINGLE SPEED AIR CONDITIONER DH O Y1 Y Y2 Y Y Y2 O W2 Y1 W2 W W1 W1 W2 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF ON OFF See Notes 2 and 7 on page 9 COOL STAGE 1 FAN HEAT STAGE 1 N A HEAT STAGE 2 24 VAC HOT R G W W1 Y1 W2 O W2 B S1 ...

Страница 7: ...MOSTAT SPLICE BOX YEL ORN BRN C O W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION WHT GRN RED COOL HEAT STAGE 1 HEAT STAGE 2 RVS COOLING N A FAN 24 VAC HOT SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 3 9 and 10 on page 9 COOL STAGE 1 FAN HEAT STAGE 1 COOL STAGE 2 N A 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C MODEL 1300 ...

Страница 8: ...A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y Y2 C W2 MODEL 1300 THERMOSTAT SINGLE STAGE FURNACE TWO SPEED HEAT PUMP R Y1 O R W3 G W SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 3 8 and 9 on page 9 COOL HEAT STAGE 1 RVS COOLING HEAT STAGE 3 COOL HEAT STAGE 2 FAN 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C W2 MODEL 1300 THERMOSTAT...

Страница 9: ...at operation via furnace control algorithm Refer to indoor equipment installation instructions for proper setup 7 Refer to fan coil installation instructions for proper wiring 8 Select the ZONE position on the 2 speed heat pump control board 9 Refer to outdoor equipment installation instructions for proper setup 10 Program thermostat to bring on fan G with any heat W selec tion See Step 5 Set Ther...

Страница 10: ...gu ration value larger on the left of the thermostat display will flash Change the configuration value with the Up and Down Arrow buttons Press the Set Time Temp button again to save the configuration and change a different configuration Record all chosen configuration options on page 16 Press the End but ton to exit Configuration mode The thermostat will automati cally exit Configuration mode if ...

Страница 11: ...K RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED LEGEND TB Terminal Block Factory Wiring Field Wiring TB S1 S2 TO THERMOSTAT RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION ...

Страница 12: ...just the offset or until the thermostat temperature matches room temperature ENABLE AUTO MODE Option No 15 The enable au to mode selection allows the installer to enable or disable AUTO mode automatic changeover between heat and cool When disabled AUTO indicator does not appear when succes sive presses of the Mode button are used to move between OFF HEAT COOL and E HEAT in heat pump systems Factor...

Страница 13: ...to 4 time periods WAKE DAY EVE SLEEP Each time period has a start time heating set point and cooling set point Fill in the schedule table on page 16 as an aid to programming the daily schedules PROGRAMMING MODE To program the daily schedules perform the following procedure 1 Enter Programming mode by pressing the Program button The PROGRAMMING indicator will appear on the thermostat display The cu...

Страница 14: ...the Fan and Up Ar row buttons together increase temperature Fifteen Minute Cycle Timer This timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle Its function is to assure that equipment is not cycled more than 4 times per hour This timer is defeated for 1 cycle when the desired temperature is manual ly changed It can also be defeat...

Страница 15: ...at should be replaced E2 on temperature display Brownout condition or too low of voltage to thermostat Double check wiring and check for 24 vac between R and C E2 will clear 15 seconds after proper voltage is restored E3 on temperature display Outdoor temperature reading out of range and needed for Option No 8 Check out door temperature sensor and its wiring Clean Filter on temperature display Aft...

Страница 16: ...t Recovery OFF enable ON disable Switch C Heat Pump Operation OFF enable ON disable Switch D Intelligent Heat Staging OFF disable ON enable 01 Anticipator Adjustment 1 9 factory default 3 02 Clean Filter Timer Adjustment OF or 1 9 factory default 2 03 Farenheit or Celsius Operation F or C factory default F 04 Enable Fan G On with Any Heat W OF or On factory default OF 05 07 N A 08 Auxiliary Heat L...

Отзывы: