SETTINGS – FORCED STAGE UP
31
DEFINITION
DEPENDENCIES
FUNCTION
Pressing the Forced Stage Up
field in the “System Settings
Screen” will invoke the “Forced
Stage Up Screen” which will allow
a time choice from OFF to 10
minutes to 120 minutes for the
forced stage up timer
functionality, adjustable in 10
minute increments.
Multiple heating stages or
multiple cooling stages must
exist for this feature to be
used.
If time in a current demanded stage reaches the forced
stage up selected time, the thermostat will stage up to
the next available stage of capacity (even if differential
demand is not met).