SETTINGS – STAGE DELAY
30
DEFINITION
DEPENDENCIES
FUNCTION
Pressing the Stage Delay field in
the “System Settings Screen” will
invoke the “Stage Delay Screen”
which will allow a time choice
from 2 minutes to 15 minutes for
the stage delay functionality,
adjustable in 1 minute
increments.
Multiple heating stages or
multiple cooling stages must
exist for this feature to be
used.
The minimum amount of time the current stage must
be energized before staging up to the next stage of
capacity. If the system demand is greater than three
degrees then this configuration is ignored for the
current heating or cooling cycle because the staging
timers are canceled to allow full equipment capacity to
meet the large demand.