Installation Guide

69-2268—03 

570-219

Shaded areas below apply only to 

P340-1320

.

0240

First stage heat  

cycle rate (CPH= 

cycles per hour)

5  Gas or oil furnaces of less than 90% efficiency

1  Steam or gravity systems
3  Hot water systems & furnaces of 90%+ efficiency
9  Electric furnaces
 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0250

Second stage heat 

cycle rate (CPH)

5  Gas or oil furnaces of less than 90% efficiency

1

 

Steam or gravity systems

3

 

Hot water systems & furnaces of 90%+ efficiency

9

 

Electric furnaces

 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0260

Third stage heat  

cycle rate (CPH)

9  Electric auxiliary heat or electric furnaces

1

 

Steam or gravity systems

3

 

Hot water systems & furnaces of 90%+ efficiency

5

 

Gas or oil furnaces of less than 90% efficiency

 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0270

Emergency heat 

cycle rate (CPH)

9  Electric emergency heat

1

 

Steam or gravity systems

3

 

Hot water systems & furnaces of 90%+ efficiency

5

 

Gas or oil furnaces of less than 90% efficiency

 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0280

Backlight

0  Backlight on for approx. 8 seconds after keypress

1

 

Backlight always on low intensity, full bright after key-
press (requires 24VAC connection)

0300

Manual/Auto 

changeover

0  Manual changeover (Heat/Cool/Off)

1

 

Automatic changeover (Heat/Cool/Auto/Off)

0310

Auto changeover 

deadband

3   Heat/cool temperature 3°F apart (1.5°C)

 

 

** See page 11 

[Other options: 2-9 (2°F to 9°F/1°C to 5°C)]

0320

Temperature 

display

0  Fahrenheit

1

 

Celsius

0330

Daylight savings

2  Auto-change to daylight savings time

 (2007 and be-

yond, for areas that use the new 2007 DST calendar)

1  Auto-change to daylight savings time (through 2006, and 

for areas that do not use the new 2007 DST calendar)

0

 

Daylight savings time is turned off

0340

Remote sensor

0  No remote sensor

1

 

Outdoor sensor (display only)

2

 

Outdoor control sensor (select heat pumps)   ** See page 11

3

 

Indoor sensor

0350

Heat pump 

compressor lockout

0  No heat pump compressor lockout   ** 

See page 11

 

[Other options: 15, 20, 25, 30, 35, 40, 45°F (-9.5°C to 7°C)]

0360

Heat pump 

auxiliary lockout

0  No heat pump auxiliary lockout   ** 

See page 11

 

[Other options: 40, 45, 50, 55, 60°F (4.5°C to 15.5°C)]

Installer setup

Continued on next page

Setup functions

Settings & Options 

(factory default in 

bold

)

Содержание Deluxe 1C

Страница 1: ...systems power to open and close zone valves Series 20 and normally open zone valves Heat only with fan Cool only 750 mV heating systems This manual covers the following models P340 1110 For 1 Heat 1 Cool systems P340 1320 For up to 2 Heat 2 Cool heat cool systems or up to 3 Heat 2 Cool Heat Pump Systems Need Help Visit www Totaline com This thermostat contains a Lithium battery which may contain P...

Страница 2: ...ntrol in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power before beginning installation Drill 3 16 holes for drywall Drill 7 32 holes for plaster Must be installed by a trained experienced technician Read these instructions carefully Failure to f...

Страница 3: ...ay Y 1st stage compressor contactor Y2 2nd stage compressor contactor G Fan relay S1 Optional outdoor or remote sensor S2 Optional outdoor or remote sensor Heat Pump Terminal Letters R Heating power Connect to secondary side of heating system transformer Rc Cooling power Connect to secondary side of cooling system transformer C Common wire from secondary side of cooling system transformer Y 1st st...

Страница 4: ...stem 2 transformers Rc Power cooling transformer 1 2 R Power heating transformer 1 2 W Heat relay Y Compressor contactor G Fan relay C 24VAC common 3 4 S1 Optional outdoor remote sensor S2 Optional outdoor remote sensor Heat Only System With Fan Rc Power 1 R R Rc joined by jumper W Heat relay G Fan relay C 24VAC common 3 S1 Optional outdoor remote sensor S2 Optional outdoor remote sensor Cool Only...

Страница 5: ...l outdoor remote sensor S2 Optional outdoor remote sensor 3H 2C Heat Pump with auxiliary heat Y2 Compressor 2 relay L Equipment monitor 6 7 E Emergency heat relay 8 Aux Auxiliary heat relay Heat 2 8 Rc Power 1 R R Rc joined by jumper O B Changeover valve 5 Y Compressor 1 relay G Fan relay C 24VAC common 3 S1 Optional outdoor remote sensor S2 Optional outdoor remote sensor Shaded areas below apply ...

Страница 6: ...thermostat snaps into place Remove tab and mount thermostat Set date and time Press st to set time Press st to set year Press st to set date Press st to set month Installer setup Press DONE to save changes Press DONE to save and exit 1 Press SYSTEM 2 Press and hold these two buttons until the display changes 3 Change settings as required see pages 7 9 ...

Страница 7: ... 1 cool multistage conventional 10 1 heat 2 cool multistage conventional 11 2 heat 2 cool heat pump no aux heat 12 3 heat 2 cool heat pump with aux heat 0180 Fan control heating 0 Gas Oil heat equipment controls heating fan 1 Electric furnace thermostat controls heating fan 0190 Changeover valve O B terminal 0 O B terminal controls valve in cooling 1 O B terminal controls valve in heating 0200 Aux...

Страница 8: ...CPH 0280 Backlight 0 Backlight on for approx 8 seconds after keypress 1 Backlight always on low intensity full bright after key press requires 24VAC connection 0300 Manual Auto changeover 0 Manual changeover Heat Cool Off 1 Automatic changeover Heat Cool Auto Off 0310 Auto changeover deadband 3 Heat cool temperature 3 F apart 1 5 C See page 11 Other options 2 9 2 F to 9 F 1 C to 5 C 0320 Temperatu...

Страница 9: ...C Other options 51 99 F 11 C to 37 C 0640 Clock format 12 12 hour time i e 3 30 pm 24 24 hour time i e 15 30 0650 Extended fan timer heat 0 Off 90 Fan runs for 90 seconds after call for heat ends 0660 Extended fan timer cool 0 Off 90 Fan runs for 90 seconds after call for cooling ends 0670 Keypad lock 0 Keypad unlocked fully functional 1 Partially locked access to temperature settings only 2 Fully...

Страница 10: ...urns on 2 Fan system 0 Fan turns off 1 Fan turns on 3 Heating system 0 Heat and fan turn off 1 Heat turns on fan on if Function 0170 is set for heat pump or if Function 0180 is set to 1 See page 6 2 Second stage heat turns on 3 Third stage heat turns on 4 Emergency heating system 0 Heat and fan turn off 1 Heat and fan turn on 2 Second stage heat turns on Auxiliary heat System test System status CA...

Страница 11: ...ptional outdoor sensor you can select a compressor lockout temperature Function 0350 When the outdoor temperature is below the lockout temperature only the auxiliary heat operates When the outdoor temperature is above the lockout temperature only the compressor operates Heat Pump Auxiliary Lockouts with electric heat backup If the thermostat is installed with an optional outdoor sensor you can sel...

Страница 12: ...90 non condensing Physical Dimensions 4 9 16 H x 6 W x 1 3 8 D 116 mm H x 152 mm W x 35 mm D Electrical Ratings Terminal Voltage 50 60Hz Running Current W Heating 20 30 Vac 0 02 1 0 A Powerpile 750 mV DC 100 mA DC W2 Heating 20 30 Vac 0 02 0 6 A Y Cooling 20 30 Vac 0 02 1 0 A Y2 Cooling 20 30 Vac 0 02 0 6 A Aux Auxiliary heat 20 30 Vac 0 02 1 0 A O B Changeover 20 30 Vac 0 02 0 6 A E Emergency hea...

Отзывы: