Installation Guide
69-2268—03
8
570-219
Shaded areas below apply only to
P340-1320
.
0240
First stage heat
cycle rate (CPH=
cycles per hour)
5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0250
Second stage heat
cycle rate (CPH)
5 Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0260
Third stage heat
cycle rate (CPH)
9 Electric auxiliary heat or electric furnaces
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
5
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0270
Emergency heat
cycle rate (CPH)
9 Electric emergency heat
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
5
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0280
Backlight
0 Backlight on for approx. 8 seconds after keypress
1
Backlight always on low intensity, full bright after key-
press (requires 24VAC connection)
0300
Manual/Auto
changeover
0 Manual changeover (Heat/Cool/Off)
1
Automatic changeover (Heat/Cool/Auto/Off)
0310
Auto changeover
deadband
3 Heat/cool temperature 3°F apart (1.5°C)
** See page 11
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)]
0320
Temperature
display
0 Fahrenheit
1
Celsius
0330
Daylight savings
2 Auto-change to daylight savings time
(2007 and be-
yond, for areas that use the new 2007 DST calendar)
1 Auto-change to daylight savings time (through 2006, and
for areas that do not use the new 2007 DST calendar)
0
Daylight savings time is turned off
0340
Remote sensor
0 No remote sensor
1
Outdoor sensor (display only)
2
Outdoor control sensor (select heat pumps) ** See page 11
3
Indoor sensor
0350
Heat pump
compressor lockout
0 No heat pump compressor lockout **
See page 11
[Other options: 15, 20, 25, 30, 35, 40, 45°F (-9.5°C to 7°C)]
0360
Heat pump
auxiliary lockout
0 No heat pump auxiliary lockout **
See page 11
[Other options: 40, 45, 50, 55, 60°F (4.5°C to 15.5°C)]
Installer setup
Continued on next page
Setup functions
Settings & Options
(factory default in