Total Protection Solutions LoadTrack TK-LTL120P-30A Скачать руководство пользователя страница 3

1. System Configuration Verification

Confirm that the voltage(s) and service configuration shown on the LoadTrack LTL product label are consistent with the
voltage and service configuration of the facility. A model number is on the side of the LoadTrack LTL unit. Each model num-
ber corresponds to the configurations printed in Table 1:
Example of a SPD model number in Table 1: TK-LTL-120P-30A

Pre-Installation Checklist

Prior to installation, verify that the voltage rating(s) of the intended LoadTrack surge protective device (SPD) match those of
the electrical system or circuit to which the product is to be installed. 

Table 1

The Two-Port LoadTrack SPD is provided with a Power ON indicator. When power is applied to the LoadTrack SPD, the Power
ON indicator will illuminate. When power is removed from the LoadTrack series SPD, the Power ON indicator will extin-
guish.

The LoadTrack SPD is intended to be installed and operated in an ambient environment that does not exceed 104°F (+40°C),
and does not contain conductive liquids or combustible dusts, fibers, vapors, or liquids.

The environment should also maintain a humidity range of 5% – 95% (non-condensing).

The LoadTrack SPD is intended to be stored in a dry location where the temperature range does not exceed -40°F to +140°F
(-40°C to +60°C).

WARNING: Do not HIPOT the LoadTrack LTL unit or the electrical system that the LoadTrack LTL is connect-
ed to without disconnecting the LoadTrack LTL conductors including phases, neutral and ground.

LOADTRACK LTL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

3

IMPORTANT SAFETY INSTRUCTIONS   All work must be performed by licensed and qualified personnel. The electrical
system must be properly grounded in accordance with the U.S. National Electrical Code, state and local codes or other
applicable codes for this SPD to function properly.  This device is suitable for installation where the available short cir-
cuit current is 65,000 rms symmetrical amperes at 480VAC or less.

WARNING:  HAZARDOUS  VOLTAGES  PRESENT    Improper  installation  or  misapplication  may  result  in 
serious personnel injury and/or damage to electrical system. Read the complete installation instructions before
proceeding with installation. Remove all power to the electrical panel before installing or servicing the surge
protective device (SPD).

!

   BEFORE INSTALLATION

   

LOADTRACK SPD MODEL NUMBER

NOMINAL VOLTAGE (L-N)             

    

    

TK-LTL120P-30A                                                                                              

120

   TK-LTL220P-30A                                                                       

                     

220

   TK-LTL277P-30A                                                                       

                     

277

    LOADTRACK SPD MODEL NUMBER

NOMINAL VOLTAGE (L-N, L-L)

    
    
    

TK-LTL120S-30A                                                                       

                  

120/240

   TK-LTL220S-30A                                                                       

                 

220/380

   TK-LTL277S-30A                                                                       

                 

277/480

    

                                                                                                                                                                         

!

Содержание LoadTrack TK-LTL120P-30A

Страница 1: ...evices Installation Operation and Maintenance Manual LOADTRACK LTL INSTALLATION OPERATION AND MAINTENANCE MANUAL PN 750 0071 002 A00 LoadTrack LTL P O Box 3760 Winter Park FL 32790 USA TEL 800 647 191...

Страница 2: ...System Configuration Verification Pre installation Checklist LoadTrack SPD Model Numbers Mounting Electrical Connections Service Configurations Single Phase Split Phase Dimensional Specifications Sta...

Страница 3: ...s intended to be stored in a dry location where the temperature range does not exceed 40 F to 140 F 40 C to 60 C WARNING Do not HIPOT the LoadTrack LTL unit or the electrical system that the LoadTrack...

Страница 4: ...mounting hardware is 16 in lbs 1 8Nm Electrical Connections 1 The LoadTrack SPD must be protected via a circuit breaker with a maximum capacity of 30 amps 2 Determine the location of the AC source su...

Страница 5: ...Service Configurations Figure 1 Single Phase Figure 2 Split Phase Use only the L1 Terminal lug for the phase wires input output when connecting a single phase configuration Match the corresponding L1...

Страница 6: ...7 mm 0 38 in 9 7 mm Dimensional Specifications Figure 3 STANDARDS AND LISTINGS Listed by ETL to UL 1449 3rd Edition 2009 Revision Type 4 for Type 2 SPD applications cUL and UL 1283 Compliant to IEEE C...

Страница 7: ...ty under this warranty for problems or defects directly or indirectly caused by misuse of the Product alteration of the Product including removal of any warning labels accidents improper installation...

Страница 8: ...2014 TOTAL PROTECTION SOLUTIONS LLC PRINTED IN USA ALL RIGHTS RESERVED PN 750 0071 002 A01 072414 P O Box 3760 Winter Park FL 32790 USA www TPSsurge com 1 800 647 1911...

Отзывы: