– 20 –
7-4-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the
desired position.
(2) When the AUTO button is pushed, the louver
vertically swings within range of 25deg.
And the louver position is stored in the micro-
computer, and at the next operation, the louvers
will be set to the stored position automatically at
the next operation.
7-4-2. Cool Airflow Control
(1) If the indoor heat-exchanger temperature de-
tected by the indoor heat-exchanger sensor is
20°C or below, the indoor fan stops and if the
temperature rises to 25°C (RAS-10YKH-E, RAS-
10YKH-ES), 35°C (RAS-13YKH-E, RAS-13YKH-
ES) or above, the fan is restarted. The details are
in 7-10.
7-5. AUTO Operation
(MODE of the remote control : AUTO)
(1) One of the 3 modes, Cooling, Fan only and
Heating is selected according to room tempera-
ture at which operation is to start, as shown in
Fig. 7-5-1. The Fan mode will continue until room
temperature reaches a level at which another
mode is selected.
7-5-1. Temporary Auto
When the TEMPORARY button is pushed (1 sec),
the set temperature is fixed at 24°C and controlled in
accordance with the chart shown in Fig. 7-5-1.
Cooling mode
Cooling mode
Fan only mode
Heating mode
+4
+1
–1
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
The Louver moved downward.
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
(Only the indoor fan operates at Low speed)
(The same heating mode as the room temperature control is set at set temp. +1˚C)
(Room temp.
–
Set temp.)
Fig. 7-5-1