80
WX9 ASD Installation and Operation Manual
Forward/Reverse Run Priority When Both Are Closed
Program
Terminal
Input Special Functions
The
Forward/Reverse Priority Selection
determines the operation of the ASD
if both the
F
and
R
control terminals are activated.
Settings:
0 — Reverse
1 — Suspend
The waveforms depict the motor response for all combinations of the
F
and
R
terminal settings if the
Reverse
option is chosen.
The
Suspend
setting will decelerate the motor to a stop regardless of the
rotation direction when both the
F
and
R
control terminals are activated.
Direct Access Number — F105
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Input Terminal Priority Selection
Program
Terminal
Input Special Functions
This parameter is used to allow the
Jog
and
DC Injection Braking
input
signals to control the ASD when received via the
Terminal Board
even though
the system is in the
Hand
mode.
With this parameter enabled,
a
Jog
command or a
DC Injection Braking
command received from the
Terminal Board
will receive priority over
commands from the
EOI
.
See
Jog Frequency
F260)
for additional information on using the
Jog
function.
See
for additional information on
DC Injection Braking
.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F106
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
16-Bit Binary/BCD Input Selection
Program
Terminal
Input Special Functions
The
Extended Terminal Function
is used with the optional
ASD-Multicom
card only. This parameter defines the format of the binary or BCD data when
using the option card.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the
Terminal Board
as binary bits 0 – 3 (
–
The
Frequency Mode 1
(
) must be set to
Binary/BCD (option)
.
For proper scaling of the binary or BCD input, parameters
–
must be
configured [
BIN Reference Point 1
,
BIN Point 1 Frequency, BIN Reference
Point 2
, and
BIN Point 2 Frequency
].
Direct Access Number — F107
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......