WX9 ASD Installation and Operation Manual
19
System Grounding
Proper grounding helps to prevent electrical shock and to reduce electrical noise. The ASD is designed
to be grounded in accordance with the
NEC Article 250
or the
Canadian Electrical Code
(CEC)
Section 10/Part One
.
The grounding conductor shall be sized in accordance with the
NEC Article 250-122
or the
CEC Part
One-Table 6
.
— Metal Conduit Is Not An Acceptable Ground —
The input, output, and control lines of the system shall be run in separate metal conduits and each shall
have its own ground conductor.
ASDs produce high-frequency noise — take steps to avoid the negative effects of noise. Listed below
are some examples of measures that will help combat noise problems.
•
DO NOT
install the input power and output power wires in the same duct or in parallel with each
other, and
DO NOT
bind them together.
•
DO NOT
install the input/output power wires and the wires of the control circuit in the same duct
or in parallel with each other, and
DO NOT
bind them together.
•
Use shielded wires or twisted wires for the control circuits.
•
Ensure that the grounding terminals (G/E) of the ASD are securely connected to ground.
•
Install noise filters as required.
Lead Length Specifications
Adhere to the NEC and any local codes during the installation of ASD/motor systems. Excessive lead
lengths may adversely effect the performance of the motor. Special cables are not required. Lead lengths
from the ASD to the motor in excess of those listed in
may require filters to be added to the
output of the ASD.
lists the suggested maximum lead lengths for the listed motor voltages.
Note:
Contact the TIC Customer Support Center for application assistance when using lead
lengths in excess of those listed.
Exceeding the peak voltage rating or the allowable thermal rise time of the motor
insulation will reduce the life expectancy of the motor.
For proper operation, the carrier frequency must be 2.2 kHz or above except when
operating in the
Constant Torque
,
Variable Torque
, or the
5-Point Setting
modes.
Table 1. Lead Length Specifications.
Model
PWM Carrier
Frequency
NEMA MG1 Part 31
Compliant Motors
NEMA MG1 Part 30
Compliant Motors
460 Volt
5 kHz
600 feet
200 feet
kHz
300 feet
100 feet
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......