WX9 ASD Installation and Operation Manual
Sel. No
.
Terminal Selection Descriptions
NO
NC
66
67
Binary Bit 6
— Used in conjunction with terminal setting 54/55 above.
68
69
Binary Bit 7
— Used in conjunction with terminal setting 54/55 above.
76
77
User Fault 1
— No operation.
78
79
User Fault 2
— No operation.
80
81
User Fault 3
— No operation.
82
83
User Fault 4
— No operation.
86
87
Binary Data Write
— This terminal serves two functions:
1) While operating in the
Use Binary/BCD input
mode, each momentary connection of this terminal to
CC
transfers the
speed/torque
Binary Bit
(0 – MSB)
settings to the motor.
2) The
UP/DOWN
frequency command will be saved during power down or reset by setting
to
Store
and setting an input
terminal to
43:Binary Data Write
. If the drive is running and the
Binary Data Write
terminal
is active when an event occurs
(Fault, Power Off), the
UP/DOWN
frequency command will be restored upon power-up or reset.
88
89
UP/DOWN Frequency (up) —
Increases the speed of the motor for the duration of activation until reaching the
Upper-Limit
setting or increases the speed of the motor in steps (see
for additional information on this feature).
90
91
UP/DOWN Frequency (down) —
Decreases the speed of the motor for the duration of activation until reaching the
Lower-
Limit
setting or decreases the speed of the motor in steps (see
for additional information on this feature).
92
93
UP/DOWN Frequency (clear) —
Initiates a 0 Hz output command while operating in the
UP/DOWN Frequency
speed
control mode. If operating with an activated
UP/DOWN Frequency
(up or down) terminal, the output goes to the
Lower-
Limit
(
) setting.
94
95
Push Run
— Runs the motor for the duration of the activation at the configured speed and direction.
96
97
Push Stop
— Stops the motor for the duration of the activation. Motor resumes normal operation upon deactivation.
98
99
Forward/Reverse Selection
— Operates in conjunction with another terminal being set to the
Run/Stop
(50) function. When
configured to
Run
(
Run/Stop
to
CC
), the make-or-break of this connection to
CC
changes the direction of the motor.
100
101
Run/Stop Command
— Enables the motor to run when activated and disables the motor when deactivated.
102
103
Commercial Power/ASD Switching
— Initiates the ASD-to-Commercial Power switching function. See
information on this feature.
104
105
Frequency Command Priority Switching
— Connecting this terminal to
CC
allows for the frequency control to be switched
from the frequency command source selected as
Frequency Mode 1
to
Frequency Mode 2
. This function is enabled by setting
the
Frequency Priority Selection
to
Frequency Source Priority Switching
and is located at Program
Fundamental
Parameters
Standard Mode Selection.
106
107
Terminal Frequency Priority
— Overrides the
setting and assigns speed control to the
Terminal Board.
108
109
Terminal Command Priority
— Overrides the
setting and assigns command control to the
Terminal Board
.
110
111
Parameter Edit Enable
— Allows for the override of the lock out parameter setting allowing for parameter editing.
112
113
Control Switching (speed/torque)
— Toggles the system to and from the speed control and torque control modes.
114
115
Deviation Counter Clear
— Clears the
Deviation Counter
when operating in the
Position Control
mode.
116
117
Position Control Forward Limit LS
— Connecting this terminal to
CC
will immediately stop the drive and hold its position.
If the connection remains, the drive will time-out and trip. This function is normally used for over-travel conditions.
Note:
NO/NC = Normally Open/Normally Closed.
Note:
Selection numbers are used when configuring the discrete input terminals via communications. They differentiate the Normally
Open and Normally Closed contact settings.
Table 10. Discrete Input Terminal Assignment Selections and Descriptions. (Continued)
Binary
Data
Write
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......