– 22 –
• Use the polyvinyl chloride insulated and sheathed cables for fixed wiring having
1.6 mm to 2.0 mm in diameter or 2.0 mm² to 3.1 mm² in conformity with IEC 60227-4.
(Carry out the work based on the laws, regulations and technical standards of the
country concerned.)
• Follow the following steps for wiring.
• Unfasten two cover-fixing screws of the electrical equipment box,
open the box cover, and then connect wiring firmly.
• Fit the cables from the terminal firmly with a cord clamber.
• When you need much airflow or a duct is long, change the wire connection from High to Extra High.
• Unfasten two cover-fixing screws of the electrical equipment box and open the box cover.
• Change CN6 to CN5 and CN8 to CN7 inside the Electric Parts Lid.
• It is possible to operate up to 10 units from one switch set.
CAUTION
• Use the power source corresponding to the name plate. Using a different power source may cause the
motor to burn out.
• Carry out grounding work according to the laws and regulations of the country concerned and the technical
standard.
• After completion of wiring, check again there are no wrong wirings before power ON.
Ring
terminal
Secure wire
properly
Stranded
wire
Electric Parts Lid
Cover-fixing screws of the
Electric Parts Lid
(CN8)
(CN8)
(CN8)
(CN8)
Switching Connector
1 2 3 4 5 6 7
1 2 3 4 5 6 7 8
1
2
3
4
5
6
7
1 2 3 4 5
1 2 3
4
5
1
2
3
4
5
6
7 8
(Srcond main body)
Third main body
Power Source
3
1
4
1
NC
NO
CM
CN8
CN6
CN5
CN7
NO
NC
CM
NO
NC
CM
NO
CM
NO
NC
CM
TM1
4
3
2
1
6
7
5
COMMON
L
N
LOW
HIGH
DAMPER
4
3
2
1
6
7
5
TM1
COMMON
L
N
LOW
HIGH
DAMPER
(1)
(2)
(3)
(4)
(5)
(6)
(LINE)
(NEUTRAL)
Operation Switch
(1) 0 (OFF)
(2) 1 (ON)
Air Flow Switch
(3) High
(4) Low
Divide the power lines running
to the switch and the main unit.
On the product. do not attach
more then one cable to each
terminal.
Function Select Switch
(5) Heat Exchange
Ventilation
(6) Normal Ventilation
To find out the function
of each switch.
VN-800SE
220-240V~50Hz/
220V~60Hz
220-240V~50Hz
VN-1KSAE
Model
Power Source
VN-800SE
8.0µF 450VAC
VN-1KSAE
10.0µF 450VAC
Model
Capacitor
RY4
RY4
RY5
RY5
RY2
RY2
RY3
RY3
RY1
RY1
MS
Power Source
Supply
Air Fan
Exhaust
Air Fan
Red
Orange
Capacitor
Red
Orange
Capacitor
Damper
Motor
Black
Common
Black
Common
Yellow
Low
Yellow
Low
Blue
High
Blue
High
Whte
Extra
High
Whte
Extra
High
Blue
Blac
k
Yello
w
(Heat Exchange)
White
(Nor
mal)
CN–
SAFM
CN–
EAFM
CN–DM
Switch
(To be procured
locally)
Содержание VN-1KSAE
Страница 32: ......