Inspection of the new UPS equipment
Upon receipt of the UPS, a careful inspection for shipping damage should be made.
After Uncrating:
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred
during shipment, keep all original crating and packing materials for return to shipping agent.
Warranty will not apply to units which are damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate
conform to the order specifications.
Storage of UPS Equipment
If the UPS equipment is to be subject to long or short term storage the following guidelines
should be used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high humidity.
2) Storage in sites subject to exposure of high levels of dust or metal particles
3) Storage on inclined floor surfaces or in sites subject to excessive vibration.
Before Storing:
1) Allow UPS to be operated for 24 hrs. to ensure that the batteries are fully charged.
2) Stop the unit (see "Stopping the UPS" on page 41).
3) Place the unit's MCCB switch (see pages 45-46 for location) in the "off" position.
Storing:
1) Store within a temperature range of -20 ~ 40° C (-4 to 104° F).
2) For best results, store the UPS in the original shipping container and place on a wood or
metal pallet.
3) The optimum storage temperature is 21° C (70° F). Higher ambient temperatures
cause UPS batteries to need recharging more frequently.
After Storing:
1) If stored in an ambient temperature under 20° C (68° F), recharge the batteries every 9
months.
2) If stored in an ambient temperature of 20° to 30° C (68° to 86° F), recharge the batteries
every 6 months.
3) If stored in an ambient temperature of 30° to 40° C (86° to 104° F), recharge the batteries
every 3 months.
Disposal
Please contact your state environmental agency for details on disposal of electrical
components and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly.
Please help our Earth by contacting the environmental protection agencies in your area, the battery
manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling.