Jump frequency - jumping resonant frequencies
H
: Jump frequency 1
H
: Jumping width 1
H
: Jump frequency 2
H
: Jumping width 2
H
: Jump frequency 3
H
: Jumping width 3
•
Function
Resonance due to the natural frequency of the mechanical system can be avoided by jumping the
resonant frequency during operation. During jumping, hysteresis characteristics with respect to the jump
frequency are given to the motor.
Jumping width 1 (
H
)
Jumping width 2 (
H
)
Jumping width 3 (
H
)
Jump frequency 3
(
H
)
Jump frequency 1 (
H
)
Jump frequency 2 (
H
)
Output command frequency
(Hz)
Frequency setting signal
0
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Jump frequency 1
0.0-
HJ
(Hz)
0.0
H
Jumping width 1
0.0-30.0 (Hz)
0.0
H
Jump frequency 2
0.0-
HJ
(Hz)
0.0
H
Jumping width 2
0.0-30.0 (Hz)
0.0
H
Jump frequency 3
0.0-
HJ
(Hz)
0.0
H
Jumping width 3
0.0-30.0 (Hz)
0.0
+
Do not set the jump parameters, if multiple jump frequency setting width overlap.
+
During acceleration or deceleration, the jumping function is disabled for the operation frequency.
Содержание TOSVERT VF-FS1 Series
Страница 2: ......
Страница 15: ...E6581381 A 3 1 1 3 Names and functions 1 3 1 Outside view Operation panel ...
Страница 18: ...E6581381 A 6 1 VFFS1 2004 2037PM VFFS1 4004 4055PL Note EMC plate is supplied as standard ...
Страница 36: ......
Страница 39: ...E6581381 B 3 2 2 2 1 Standard connection diagram 1 This diagram shows a standard wiring of the main circuit ...
Страница 40: ...E6581381 B 4 2 2 2 2 Standard connection diagram 2 ...
Страница 54: ......
Страница 56: ...E6581381 D 2 4 4 1 Flow of status monitor mode Flow of monitor as following ...
Страница 66: ......
Страница 180: ......
Страница 196: ......
Страница 208: ......
Страница 233: ...E6581381 L 5 12 Outline drawing Fig A Fig B Fig C Fig D ...
Страница 242: ......
Страница 248: ......
Страница 251: ......