Device Type / Capacity DN Code setting (Requires wired Remote Controller)
•
Follow the basic operation Procedure (
1
→
2
→
3
→
4
) outlined above.
•
The interface uses a new Device Type DN Code 10_55. This is set at the factory.
•
The installer must set Capacity Code (DN Code 11). As default this is configured
as a 8ton model at the factory (DN 10_23). See table on next page.
Capacity code
012
015
018
021
024
030
036
042
048
060
072
096
168
192
336
384
Capacity (Ton)
1
1.25
1.5
1.75
2
2.5
3
3.5
4
5
6
8
14
16
28
32
Capacity Code (DN 11)
05
07
09
10
11
13
15
16
17
19
21
23
27
28
37
39
RBM-A***GUL
0121
0301
0601
0961
1921
1921 X 2
■Summary of Inputs and Outputs (Standard)
Description
Type
Terminal
VRF Power Supply
208/230 VAC
L1 & L2 & G (Ground)
VRF Main Bus (U1/U2)
Serial
U1/U2/G (Shield wire)
Sub-Bus (AB) : Remote controller wiring
Serial
A / B
ON / OFF input
DI
C1 & C2
Safety contact input (P10)
DI (Normal Close)
C5 & C6
Fan error input (L30)
DI
C7 & C8
Fan Operation (Contact Rating: 250VAC 6A)
DO
D1 & D2 (KP2)
Alarm output (Contact Rating: 250VAC 6A)
DO
D5 & D6 (KP3)
Thermo ON (NC) output (Contact Rating : 250VAC 6A)
DO
D15 & D16 (KP8)
Secondary Heating Output / Cooling output
DO
D19 & D20 (KP9)
■
Main Indoor PCB (MCC-1570): CN60/CN61/CN82 Configuration
•Digital
output functions are available from the CN60/CN61/CN82 connector on the main indoor PCB (MCC-1570)
inside the DX-controller.
•
For ease of installation connection to the CN60/CN61/CN82 outputs are made on the relays included in the DX interface.
As the factory setting, “CN82 Pin No.4” function is cooling output function.
Secondary heating function becomes effective to set up DN code [DC]
setting data [0001 to 0010].
Factory setting :
DN code [DC :0000]
Secondary heating :
DN code [DC : 0001 to 0010]
CN82, Pin No.4
➡
Cooling output function
CN82, Pin No.4
➡
Secondary heating output function
CN60/CN61/CN82 Output
Output Function
Relay Number
CN60.1+6
Fan operation output
KP2
CN61.5+6
Alarm output
KP3
CN82.6+3
Thermo ON output
KP8
CN82.6+4
Cooling output /
Secondary heating output
KP9
11
<How to enter the DN setting>
1.Push the button to display
the menu screen.
2.Push and hold the
and
button at the same time for more
than 4 seconds to display the “Field setting
menu” .
3. Select “7. DN setting” on the “Field setting
menu
”, then push the [F2] button to set.