18
7
APPLICABLE CONTROLS / BMS INTERGRATION
A wired remote control is required during installation of the RA control DX-Controller.
Dx-Controller Configuration
• The Dx-Controller (TCB-IFDA1GUL) main PCB is common
for 0-10V type (TCB-IFDD1GUL : Analogue input type) .
• As default this is configured as a RA control type in this model.
Do not change the DIP-SW501 on MCC-1570.
REQUIREMENT
•
When you use this air conditioner for the first time, it takes approx. 5 minutes
until the remote control becomes available after power-on. This is normal.
<When the power is turned on for the first time after installation>
It takes
approx. 5 minutes
until the remote control becomes available.
<When the power is turned on for the second (or later) time>
It takes
approx. 1 minute
until the remote control becomes available.
•
Normal settings were made when the unit was shipped from factory.
Change the Dx-Controller as required.
•
Use the wired remote control to change the settings.
•
The settings cannot be changed using the wireless remote control,
sub remote control, or remote control-less system (for central remote
control only). Therefore, install the wired remote control to change
the settings.
Changing of settings for applicable controls
Basic procedure for changing settings
Change the settings while the air conditioner is not working.
(Be sure to stop the air conditioner before making settings).
Procedure 1
Push the + + button to s
elect “7. DN setting” on the
“Field setting menu” screen, then push “Set” [F2] button.
Move the cursor to select “DN code” with the “<” [F1] button, then set “DN code”
With the button.
Move the cursor to select “data” with the “>” [F2] button, then set “data” with the
button.
Procedure 2
Refer to this installation manual for details about the DN code and data.
Procedure 3
Push the button to set the other DN cod
es. After “Continue?”
is displayed on the screen, push the “Yes” [F1] button
Procedure 4
Push he “No” [F2] button to finish the setting operation. appears on the
screen for a while, then the screen return to the “Field setting menu” screen.
System
RA control
0-10V
SW501_1
OFF
OFF
SW501_2
OFF
ON