6. List of Error Messages
Message
Contents
Illegal Connection Type.
In the connection setting, connection type specified is other
than Ethernet or Serial.
Designate Ethernet or Serial.
Illegal data type.
In the Tag setting, illegal characters are used for the data type
designation.
Designate any of INT, DINT, UINT, UDINT, HEX, DHEX,
REAL, BOOL, BCD, or DBCD.
Illegal Parity setting.
Parity must be ODD, EVEN, or NON.
In the serial setting, illegal parity setting is designated.
Designate the parity any of odd, even, or non.
Illegal PLC model.
In the PLC setting, invalid PLC model is designated .
Set the PLC model correctly.
Illegal setting type.
Use C, CS, CM, PE, PS, PM, T, TA, or
+.
In the configuration file, other than #, C, CS, CM, PE, PS, PM,
T, TA, or + is used in the first column.
Check the configuration file.
Illegal Update Cycle setting (High-
speed/ Middle-speed/Low-speed).
In the connection setting, update cycle setting contains other
than number.
Set the update cycle correctly.
Illegal Update Cycle setting.
In the Tag setting, there is illegal update cycle setting.
Set high, middle, or low.
IP address is duplicated.
In the PLC setting, IP address is duplicated.
Set the IP address correctly.
IP address is not correct.
In the PLC setting, illegal IP address is used.
Set the IP address correctly.
Item must be separated by comma.
In the configuration file, setting items are not separated by
comma.
Separate each item by comma. Use CSV format.
Low-speed cycle must be greater than
Middle-speed cycle.
In the connection setting, low-speed update cycle is smaller
than the middle-speed update cycle.
Set the low-speed update cycle greater than middle-speed.
Maximum number of TAGs per High-
speed/Middle-speed/Low-speed cycle
of the [PLC Name] is 32.
In the configuration file, the number of Tags for a PLC per
each update cycle exceeds 32. (Individual address Tag)
The maximum number of Tags available in 1 PLC is 32 per
each update cycle.
Maximum number of TAGs per High-
speed/Middle-speed/Low-speed cycle
of the [PLC Name] is 32.(1 double-word
Tag requires 2 registers)
In the configuration file, the number of Tags for a PLC per
each update cycle exceeds 32. (Individual address Tag)
Because one double-word Tag requires two registers.
Reduce the Tags.
Memory allocation error.
It could not allocate the Windows shared memory that holds
the collecting data.