6. Communication parameters

Be careful the parameter setting range, initial value, etc. may change with the inverter models.

Function

Parameter

Note

Communication
speed

f800

Communication speed must be the same in the same network
(Inverters, Host computer, RS485 units).

Parity

f801

Parity setting must be the same in the same network (Inverters, Host
computer).
In addition, None parity is not available.Select odd or even parity bit.

Inverter number

f802

Do not assign the same inverter number in the same network (Inverters,
Host computer).
Need to set the inverter number in the transmission format.

7. 

Specifications

Item

Specifications

Part number

RS4001Z-0

Service environment

Indoors. Altitude of less than 1000m (3280 ft).
Must not be exposed to direct sunlight, subjected to corrosive and/or
explosive gases, vapor, dust, chips, cutting oil, grinding agent, etc.

Ambient  temperature

From -10

°

C to +50

°

C (14

°

F to 104

°

F)

Storage temperature

From -25

°

C to +65

°

C (-13

°

F to 149

°

F)

Relative humidity

20 to 90% (no condensation allowed)

Vibration

5.9m/s

2

 or less

Cooling system

Self-cooling

8. 

Warranty

Any part of the RS485 Option Unit that proves defective will be repaired and adjusted free of charge

under the following conditions:

1. If and when a trouble occurs on the option unit properly installed and handled within one year of    

    delivery, and if the trouble is clearly attributable to defects inherent in our design and manufacture,

      the product will be repaired free of charge.

2. The warranty covers only the delivered option unit.

3. Even in the term of the warranty, repair/adjustment service will be charged for the following cases.

    1) Fault or damage resulting from misuse, unauthorized modification or repair.

    2) Fault or damage resulting from falling down of the product or traffic accident during transportation.

    3) Fault or damage originating from fire, salt water/salty breezes, some kind of gas, earthquake,

        storm or flood, lightning, abnormal supply voltage, other natural disasters.

    4) Fault or damage caused by improper use of this option unit as it is used for a purpose out of its

    original function.

4. If there is another special warranty contracted for this option unit , the special warranty has

    priority over this warranty.

Содержание RS4001Z-0

Страница 1: ...mmunication unit cannot use at TOSVERT VF S7 S7e inverter has a CPU whose version is V100 to V102 For checking the version number of the CPU refer to the Monitor paragraph in the instruction manual of the inverter C TOSHIBA CORPORATION 1998 All Rights Reserved NOTE 1 Make sure that this instruction manual is delivered to the end user of the RS485 converter unit 2 Read this manual before installing...

Страница 2: ... and please use it for future maintenance and inspection Explanation of part number of RS 485 Option Unit RS4001Z 0 Check of accessories The RS 485 Option Unit is shipped together with the following accessories in the same package On opening the packing case check to see if the following accessories are contained or not 1 Instruction manual of RS 485 Option Unit 1 copy E6580718 2 Connector termina...

Страница 3: ...fire Mandatory Wiring should be conducted after turning the inverter power off Turn off the power immediately in case any abnormalities such as smokes smells or abnormal noise are found Neglect of these conditions could lead to fire For repairs call your agency Transportation and installation Danger Prohibited Do not install or operate the inverter if it is damaged or any part is missing from it O...

Страница 4: ...onnecting connection cable make sure to hold its connector with care not to give unreasonable stress to the cable and the unit Since connectors of optional cables have locking pawls for disconnection prevention at the inverter and the Option Unit disconnect such a connector while pressing the pawl by finger for unlocking Mount the Option Unit securely on the panel otherwise it could fall and cause...

Страница 5: ...face Conforming to EIA RS485 standard Configuration 4 wire bus type terminating resistor is necessary at each end of system Communication Distance 1 000m maximum Connection Points 32 units maximum Number of ASDs per one Option Unit 2 units maximum Number of ASDs on the Same Network 64 units maximum Communication Line Isolation Not isolated Synchronization Method Start stop synchronization Communic...

Страница 6: ...er AI TWIN2 0 5 8WH AI TWIN2 0 75 8GY AI TWIN2 1 8RD AI TWIN2 1 5 8BK Others COMBICON terminal blocks such as the Phoenix Contact TMSTBP series that allows signal branching can be used in place of included terminal INVERTER 1 INVERTER 2 Communication connector Connect to the inverter s common serial conector with the option cable Setting Baud rate SW1 SW2 OFF OFF 1200 ON OFF 2400 OFF ON 4800 ON ON...

Страница 7: ...ound to a power ground or any other noise producing ground connection 6 Insert the removable terminal block back into the RS 485 Option Unit 7 Connect the communication connectors INVERTER1 and INVERTER2 of the RS 485 Option Unit to the inverter s common serial option communication connector of the with the optional cable 8 Turn on the power of the inverter 9 Set the communication parameters of th...

Страница 8: ... ground SG 6 Shield ground FG Another RS 485 Option Unit Host Computer 1 2 3 4 5 6 1 2 3 4 5 6 R R T T S S X X X X G H A B A B I E L D SW INVERTER 2 INVERTER 1 RS485 OPTION UNIT More than 5cm More than 5cm Leave a space more than 5cm on left and bottom side of option unit for connecting the communication cable Example VF A7 Common serial option connector Example VF S7 VF S7 Common serial option co...

Страница 9: ...low Make sure a space for connecting cables Use M3 screws to install RS485 Converter Unit 3 2 Hole Unit mm 45 3 2 hole 2 8 13 5 19 6 15 9 1 0 1 0 13 2 60 0 28 0 13 5 88 0 1 0 1 0 2 0 49 7 27 1 22 6 19 6 15 9 12 6 100 0 15 9 19 9 31 6 16 0 9 0 2 0 112 0 90 0 11 0 11 0 30 0 SW INVERTER 1 RS485 OPTION UNIT INVERTER 2 ...

Страница 10: ...tion allowed Vibration 5 9m s2 or less Cooling system Self cooling 8 Warranty Any part of the RS485 Option Unit that proves defective will be repaired and adjusted free of charge under the following conditions 1 If and when a trouble occurs on the option unit properly installed and handled within one year of delivery and if the trouble is clearly attributable to defects inherent in our design and ...

Отзывы: