background image

 

 
 

RemotEye III Quick Installation Guide – 63761-002 

 

 

Installing RemotEye III 

Follow these steps to install the RemotEye III internal 
card. 

1)

 

Slide the RemotEye III  internal printed circuit 
board into the extension option slot of the UPS. 
 
Secure the printed circuit board using the UPS-
supplied screws.(See Figure 1)

 

 
 
 
 

Figure 1: RemotEye III Circuit Card 

Configuration 

RemotEye III must be configured for proper operation on its network. 

Configuring the RemotEye III via Terminal 

The RemotEye III can be configured by directly connecting to the device.  

Hardware Setup 

Direct configuration is accomplished through the provided PC cable.  Follow these steps to setup 
the hardware for direct RemotEye III configuration: 

a)

 

Connect the DB9 female end of the PC cable to the terminal or workstation COM port. 

b)

 

Connect the RJ45 end of the PC cable to the COM port of the RemotEye III/Internal. 

Software Setup 

The direct configuration is accomplished by using the RS232 communication protocol.  
The direct communication can be performed from a workstation running Terminal 
Emulator Software (TES) 

Connecting to the RemotEye III via Terminal 

A direct configuration session can easily be established once the hardware and software are 
properly set up.  Follow these steps to begin configuration

Terminal Emulator Example 

To configure the RemotEye III from a Windows platform, use Hyperterminal.  Hyperterminal is a 
standard terminal emulator packaged with any Windows operating system.  Launch the 
Hyperterminal program by navigating to: 
 Start 

 Programs 

 Accessories 

 Communications 

 Hyperterminal 

 Hyperterminal,  

and follow the prompts. 
 
 

Figure 1: RemotEye III

 

Содержание RemotEye III

Страница 1: ...RemotEye III Quick Installation Guide Windows Users Document No 63761 002 Date August 2015 ...

Страница 2: ...RemotEye III Quick Installation Guide 63761 001 ...

Страница 3: ...nect the DB9 female end of the PC cable to the terminal or workstation COM port b Connect the RJ45 end of the PC cable to the COM port of the RemotEye III Internal Software Setup The direct configuration is accomplished by using the RS232 communication protocol The direct communication can be performed from a workstation running Terminal Emulator Software TES Connecting to the RemotEye III via Ter...

Страница 4: ...nd press Enter to display the RemotEye III Main Menu Default Password case sensitive ADMIN TIC RemotEye III Login Menu Enter Password The seven options provided in the RemotEye III Main Menu provide access to all system RemotEye III configuration parameters These options see the Main Menu Description on Figure 3 Console Main Menu and their submenus are discussed in more detail in the next section ...

Страница 5: ...ic Host Configuration Protocol DHCP items 1 3 will be retrieved automatically System Group Menu RemotEye III Agent Version TIC RemotEye III v1 00 Ethernet address 00 E0 D8 08 80 0D 1 Ip Address 172 18 1 63 2 Gateway Address 172 18 1 1 3 Network Mask 255 255 240 0 4 Date and Time 0 Return to previous menu Please Enter Your Choice Figure 5 Console System Group Menu Description Making the Network Con...

Страница 6: ...ve been prepared Follow these steps to begin configuration 1 Launch the web browser 2 Enter the URL for RemotEye III in the browser s address field For example http 10 0 37 189 The home page of the RemotEye III will be displayed once a connection is established See figure 6 Default Login TOSHIBA Password case sensitive ADMIN Figure 6 RemotEye III HTTP Page ...

Страница 7: ...h the upgrade file is to be sent In the RemotEye III make sure the Network Upgrade Control is enabled under RemotEye III Control and that users have the Admin login string information and Password Here is the way to manually Upgrade RemotEye Firmware 1 Web Interface Go to RemotEye III Management RemotEye III Control menu then Enable Network Upgrade Control Note To enable the Network Upgrade Contro...

Страница 8: ...olving any RemotEye III system problem that you may experience or to provide application information The Support Center can be reached at 877 867 8773 toll free or 713 466 0277 The center is open from 8 a m to 5 p m CST Monday through Friday You may also contact TOSHIBA by writing to TOSHIBA International Corporation 13131 West Little York Road Houston Texas 77041 9990 For further information on T...

Отзывы: