54
RemotEye II User Manual – 50024-014
UPS Shutdown Events
This page allows the administrator to modify the output shutdown parameters. Refer to the RemotEye II
Manual for details on the output shutdown sequence.
UPS Event
This field shows the event that to which is assigned a shutdown action
Action
This field allows the administrator to set a course of action to be taken in the event of a fault.
Available actions are:
Disabled - Action is disabled; no action will be taken.
Client Warning - A warning message will be broadcast to the connected clients.
Client Shutdown - A warning message will be broadcast and the shutdown command will be sent to the
connected clients.
UPS Output Shutdown - A warning message will be broadcast, the output shutdown command will be
sent to the connected clients, and the UPS will be set to output shutdown
Shutdown Delay (min
)
This field allows the administrator to set the delay (in minutes) of the output shutdown message broadcast
or to view the current setting.
Broadcast Notification Interval (secs)
This field allows the administrator to set the broadcast interval (in seconds) of the warning message or to
view the current setting.
Содержание RemotEye II
Страница 1: ......
Страница 2: ...RemotEye II User Manual Document Number 50024 014 August 2015 ...
Страница 110: ...RemotEye II User Manual 50024 014 109 Figure 29 RemotEye Save Log Utility Set Page ...
Страница 126: ......