Toshiba RBM-Y1123FE Скачать руководство пользователя страница 8

7

English-14

English-13

[Connection diagram]

• Power is supplied from the connected indoor unit.
• Connect the attached wires (power supply/control wiring) between the Flow Selector unit and the indoor unit.
Connect wires as shown in the below figure.
• If the distance between indoor unit and Flow Selector unit exceeds 5m, connect by using the extension cable kit

(RBC-CBK15FE). (Sold separately)

RBM-Y1123FE, RBM-Y1803FE / RBM-Y2803FE

Earth 
screw

Earth screw

Attached wire

(Power supply)

Attached wire

(Control wiring)

Power supply

1 ~ 220–240V

Indoor unit

Flow Selector unit

SVS SVS

1

2

3

4

5

SVD

R(L)

SVD

MCC-1431

MCC-1431

Control P.C. board

for indoor unit

Control P.C. board

for indoor unit

1

3

5

7

9

SVS SVSS SVDD

1

3

1

3

1

2

4

3

5

5

1

2

4

3

5

S(N)

CN01

(     )

CN10

(     )

CN67

(     )

CN02

(     )

CN81

(     )

RBM-Y2803FE only

RBM-Y2803FE only

RBM-Y2803FE  and
RBM-Y1803FE only

WHITE ORANGE

BLUE

YELLOW BROWN

RED

GREEN

BLACK

6

7

6

1

1

2

3

4

5

8

8

8

7

[Flow Selector unit]

• Remove the fixing screws (4 parts) from the cover of the Flow Selector unit.
• Connect the connector (Red) of the attached wire (power supply) to CN01 on the control P.C. board.
• Connect the ring terminal of the attached wire (power supply) to the earth screw.
• Connect the connector (Green) of the attached wire (control wiring) to CN02 on the control P.C. board.
• Secure the two attached wires with the attached cord clamp.

(Be careful not to apply tension to the wires and connectors.)

• Check that the wires are not pinched, and then attach the cover.

RBM-Y1123FE, RBM-Y1803FE

RBM-Y2803FE

Cord clamp (Control wiring)

Attached wire 
(Control wire)

Attached wire 
(Power supply)

CN02 (Green)

CN01 (Red)

Earth screw

Fixing screw 
(4 parts)

Earth screw

Cord clamp

Attached wire
(Power supply)

CN01(Red)

Control 
P.C. board

Control 
P.C. board

Fixing screw 
(4 parts)

CN02

(Green)

Cord clamp

„

„

„

„

„

System wiring diagram

Power supply
Single phase 
220

~

240V,

50Hz

Power supply
220

~

240V, 50Hz

Outdoor Power supply
380V

~

415V 3N

~

50Hz

Control wiring between indoor and outdoor units

Control wiring between outdoor units

CN

01

Earth 

terminal

Earth 

terminal

Earth 

terminal

Earth 

terminal

CN

02

CN81

U1

1

3

5

5

5

U2

U1 U2 U3 U4

L1 L2 L3 N

U5 U6

L N

A B

A B

9

8

CN

01

Earth 

terminal

Earth 

terminal

CN

02

CN81

U1

3

U2

L N

A B

A B

CN

01

Earth 

terminal

Earth 

terminal

CN

02

CN81

U1

4

4

4

3

3

7

7

7

U2

L N

A B

A B

Earth 

terminal

U1 U2

L N

A B

L N

U1
U3

U2
U4

8

8

6

8

8

Outdoor Power supply
380V

~

415V 3N

~

50Hz

Earth 

terminal

Open

2

U1 U2 U3 U4

L1 L2 L3 N

U5 U6

Control wiring between outdoor units

Header outdoor unit

Outdoor Power supply
380V

~

415V 3N

~

50Hz

Earth 

terminal

2

1

U1 U2 U3 U4

L1 L2 L3 N

U5 U6

Follower outdoor unit

2

Indoor unit

3

Flow Selector (FS) unit

4

Remote controller

5

Central remote controller

6

Pull box

7

Circuit breaker

8

Main switch

9

Group control

When connecting the plural indoor units to a FS unit.

NOTE :

Control wire and power wire between FS unit and indoor unit are the accessory parts of FS unit. (Wire length : 6m)
If the length between indoor and FS unit exceeds 5m, connect by using the connection cable kit sold separately

(RBC-CBK15FE).

6

ELECTRIC WORK

Содержание RBM-Y1123FE

Страница 1: ...Installation Manual Flow Selector unit RBM Y1123FE RBM Y1803FE RBM Y2803FE English EH99893801 2 ...

Страница 2: ...ENTS Accessory parts and Parts to be procured locally 1 1 PRECAUTIONS FOR SAFETY 1 2 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER 2 3 SELECTION OF INSTALLATION PLACE 3 4 INSTALLATION OF FLOW SELECTOR UNIT 4 5 REFRIGERANT PIPING 5 6 ELECTRIC WORK 6 1 PRECAUTIONS FOR SAFETY Ensure that all Local National and International regulations are satisfied Read this PRECAUTIONS FOR SAFETY carefully before...

Страница 3: ...rminals Conform to the regulations of the local electric company when wiring the power supply Inappropriate grounding may cause electric shock Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas If a combustible gas leaks and stays around the unit a fire may occur 2 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER This air conditioner adopts the new H...

Страница 4: ...fore avoid installing the unit at a place with quiet background sound as follows 1 Rooms with quiet background sound such as bedroom hospital or room in a hotel 2 Rooms which have no ceiling and a fabric does not block the residence space from the Flow Selector unit 3 Rooms which have opening port at the ceiling When installing the unit at the above places separate the unit from the indoor unit wi...

Страница 5: ...talled draw the pipes to the position where they are to be connected before hanging the unit Ceiling preparation Because ceiling preparation depends on the building structure consult with the architect or interior finisher After removing the ceiling panels it is important to reinforce the ceiling frames to prevent ceiling panel vibration and to keep the ceiling horizontal Installation of hanging b...

Страница 6: ...096 Gas pipe Ø9 5 Ø12 7 Ø15 9 Ø15 9 Ø22 2 Liquid pipe Ø6 4 Ø6 4 Ø9 5 Ø9 5 Ø12 7 Suction gas pipe Ø15 9 Ø15 9 Ø15 9 Ø15 9 Ø22 2 Discharge gas pipe Ø12 7 Ø12 7 Ø12 7 Ø12 7 Ø19 1 Liquid pipe Ø9 5 Ø9 5 Ø9 5 Ø9 5 Ø12 7 Material Flow Selector unit Indoor unit capacity code Indoor unit side pipe size mm Outdoor unit side pipe size mm Connectable indoor units Seamless phosphorus deoxidized copper pipe for...

Страница 7: ...the outside causes water leak Flow Selector unit Heat insulating pipe Attached Binding band Local supply Heat insulator The upper slit 6 ELECTRIC WORK WARNING 1 Using the specified wires ensure to connect the wires and fix wires securely so that the external strength of the wires do not transmit to the connecting part of the terminals Incomplete connection or fixation may cause fire etc 2 Be sure ...

Страница 8: ...pinched and then attach the cover RBM Y1123FE RBM Y1803FE RBM Y2803FE Cord clamp Control wiring Attached wire Control wire Attached wire Power supply CN02 Green CN01 Red Earth screw Fixing screw 4 parts Earth screw Cord clamp Attached wire Power supply CN01 Red Control P C board Control P C board Fixing screw 4 parts CN02 Green Cord clamp System wiring diagram Power supply Single phase 220 240V 50...

Страница 9: ...ttached wire power supply Then check the R L and S N phases and connect the wire and the lead wires with the attached wire joints Connect the ring terminal of the attached wire power supply to the earth screw Connect the connector Black of the attached wire control wiring to CN081 on the indoor P C board Secure the two attached wires with the attached cord clamp Be careful not to apply tension to ...

Страница 10: ...tor unit NOTE 1 way Air Discharge Cassette Type MMU AP SH Series wiring refer to the Under Ceiling Type page 11 1 way Air Discharge Cassette Type MMU AP YH Series Floor Standing Type MMF AP H Series R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Indoor P C board CN081 Attached wire Power supply Cord clamp Attached wire Control wiring Earth screw for Flow Selector unit Faston connec...

Страница 11: ...LECTRIC WORK 1 way Air Discharge Cassette Type MMU AP SH Series Indoor P C board R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Attached wire Power supply Power supply Cord clamp Cord clamp CN081 Black Earth screw for Flow Selector unit Earth screw Faston connection R L S N terminal block for power supply Attached wire Control wiring Under Ceiling Type MMC AP 7H Series CN81 Black I...

Страница 12: ...e front panel 3 Slightly open the lower part of the front panel and then pull the upper part of the front panel toward you to remove it from the rear plate 4 Remove the terminal cover and the clamp base 5 Insert the control wire fully into the control wired remote controller terminal block and secure it tightly with screws 6 Connect the control wire connector of the flow selector unit to the lead ...

Страница 13: ...k Cord clamp R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Indoor P C board CN081 Attached wire Control wiring Earth screw for Flow Selector unit Faston connection R L S N terminal block for power supply Attached wire Power supply Cord clamp Power supply Earth screw Air to Air Heat Exchanger with DX Coil Unit MMD VN HEXE Series 6 ELECTRIC WORK Attached wire Power supply Attached w...

Страница 14: ... control wire 8 Clamp the power supply wire with the cord clamp 9 Attach the terminal cover with a screw 10 Take the control wire out of the cable slot on the rear panel so that it produces about 600 mm from the front 11 Remove the terminal cover UP 12 Remove the LED BASE 13 Insert the control wire fully into the control Wired remote controller terminal block and secure it tightly with screws 14 C...

Страница 15: ...nge SET DATA to 01 by the timer buttons 4 Push SET button 5 Push TEST button Then the setup finished Incorrect example of connection When connecting the multiple indoor units to a single FS unit the indoor units which are connected with the multiple FS units are unavailable for the group control by a single remote controller For the indoor unit a remote controller cannot be individually connected ...

Страница 16: ...893801 2 TOSHIBA C TOSHIBA C TOSHIBA C TOSHIBA C TOSHIBA CARRIER CORPORA ARRIER CORPORA ARRIER CORPORA ARRIER CORPORA ARRIER CORPORATION TION TION TION TION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...

Отзывы: