Toshiba RBM-Y1123FE Скачать руководство пользователя страница 5

4

Refrigerant pipe connecting port 
(Liquid)

Refrigerant pipe connecting port 
(Liquid)

Refrigerant pipe connecting port 
(Suction gas)

Refrigerant pipe connecting port 
(Discharge gas)

Outdoor unit side

Indoor unit side

Refrigerant pipe connecting port 
(Gas)

Hanging bracket

320 (Hanging bolt pitch)

160

250

54

75

(120)

(120)

21

44

87

200

28

56

94

(120)

(120)

67

94

Earth screw

These coils are 
on Y1803FE only. 

79

109

77

200

68

49

159

31

190

157

39

57

Refrigerant pipe connecting port 
(Gas)

Refrigerant pipe connecting port 
(Liquid)

Refrigerant pipe connecting port 
(Suction gas)

Refrigerant pipe connecting port 
(Discharge gas)

Outdoor unit side

Indoor unit side

Refrigerant pipe connecting port 
(Liquid)

Hanging bracket

470 (Hanging bolt pitch)

400

Earth screw

(Unit:mm)

English-8

English-7

4

INSTALLATION OF FLOW SELECTOR UNIT

  WARNING

Install the unit securely in the place to sufficiently withstand the weight of the unit.

If the foundation is not sturdy enough, the unit may fall and cause personal injury.

Perform a specified installation work to guard against earth quake.

Improper installation may cause the unit to fall.

REQUIREMENT

To prevent damage on the Flow Selector unit or personal injury, follow the instructions below.
• Do not step, or put any heavy object on the packed Flow Selector unit.
• When carrying the Flow Selector unit, hold the two hanging brackets and be careful not to apply excessive force to

the refrigerant pipes.

External view

RBM-Y1123FE, RBM-Y1803FE

RBM-Y2803FE

„

„

„

„

„

Installing hanging bolts

• Considering piping and wiring after hanging the Flow Selector

unit, determine the installation position and direction.

• After determining he installation position of the Flow Selector

unit, install the hanging bolts.

• For hanging bolt pitch, see the External view.
• When the ceiling is installed, draw the pipes to the position

where they are to be connected before hanging the unit.

Ceiling preparation

Because ceiling preparation depends on the building structure, consult with the architect or interior finisher.
After removing the ceiling panels, it is important to reinforce the ceiling frames to prevent ceiling panel vibration

and to keep the ceiling horizontal.

„

„

„

„

„

Installation of hanging bolts

Use M10 (mm) or W3/8 hanging bolts (2 pcs., to be local procure).
Matching to the existing structure, set pitch according to size in the unit external view as shown below.

Procure hanging bolts and nuts locally for

installing the unit.

Anchor bolt

(Blade type 

bracket)

(Slide type 

bracket)

(Pipe hanging 

anchor bolt)

Reinforcing 

steel

Hanging bolt

Hanging bolt

Support angle

Hanging bolt

Nut

Flat washer

M10 (mm) or W3/8

M10 (mm) or W3/8

M10 (mm)

2 pieces

6 pieces

4 pieces

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Steel frame structure

Use existing angles or install new support

angles.

Existing concrete slab

Use a hole-in anchors, hole-in plugs,

or a hole-in bolts.

„

„

„

„

„

Installing Flow Selector unit

• Attach the nuts (M10 (mm) or W3/8: to be local procure) and flat washers (M10: to be local procure) to the

hanging bolts.

• Put the washers over and under the T-groove of the hanging brackets of the Flow Selector unit to hang down

the unit.

• Using a level vial, check that the four sides are horizontal. (Horizontal degree: Within 5mm).

REQUIREMENT

Install the Flow Selector unit with the correct direction as shown in the figure.
If installed with incorrect direction, the Flow Selector unit will not operate properly.

Hanging 
bolt

Level vial 
(Horizontal degree: Within 5 mm)

10 to 15mm

Flow Selector unit

M10 (mm) Flat washer

M10 (mm) Flat washer
To prevent the bolt from 
coming off, attach the 
washer just under 
the hanging bracket as 
shown in the figure. 

Procure the hanging 
bolts, washers, and 
nuts locally.

Nut 
(M10 (mm) or W3/8)

Nut 
(M10 (mm) or W3/8)

Hanging bolt 
(M10 (mm) or W3/8)

Содержание RBM-Y1123FE

Страница 1: ...Installation Manual Flow Selector unit RBM Y1123FE RBM Y1803FE RBM Y2803FE English EH99893801 2 ...

Страница 2: ...ENTS Accessory parts and Parts to be procured locally 1 1 PRECAUTIONS FOR SAFETY 1 2 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER 2 3 SELECTION OF INSTALLATION PLACE 3 4 INSTALLATION OF FLOW SELECTOR UNIT 4 5 REFRIGERANT PIPING 5 6 ELECTRIC WORK 6 1 PRECAUTIONS FOR SAFETY Ensure that all Local National and International regulations are satisfied Read this PRECAUTIONS FOR SAFETY carefully before...

Страница 3: ...rminals Conform to the regulations of the local electric company when wiring the power supply Inappropriate grounding may cause electric shock Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas If a combustible gas leaks and stays around the unit a fire may occur 2 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER This air conditioner adopts the new H...

Страница 4: ...fore avoid installing the unit at a place with quiet background sound as follows 1 Rooms with quiet background sound such as bedroom hospital or room in a hotel 2 Rooms which have no ceiling and a fabric does not block the residence space from the Flow Selector unit 3 Rooms which have opening port at the ceiling When installing the unit at the above places separate the unit from the indoor unit wi...

Страница 5: ...talled draw the pipes to the position where they are to be connected before hanging the unit Ceiling preparation Because ceiling preparation depends on the building structure consult with the architect or interior finisher After removing the ceiling panels it is important to reinforce the ceiling frames to prevent ceiling panel vibration and to keep the ceiling horizontal Installation of hanging b...

Страница 6: ...096 Gas pipe Ø9 5 Ø12 7 Ø15 9 Ø15 9 Ø22 2 Liquid pipe Ø6 4 Ø6 4 Ø9 5 Ø9 5 Ø12 7 Suction gas pipe Ø15 9 Ø15 9 Ø15 9 Ø15 9 Ø22 2 Discharge gas pipe Ø12 7 Ø12 7 Ø12 7 Ø12 7 Ø19 1 Liquid pipe Ø9 5 Ø9 5 Ø9 5 Ø9 5 Ø12 7 Material Flow Selector unit Indoor unit capacity code Indoor unit side pipe size mm Outdoor unit side pipe size mm Connectable indoor units Seamless phosphorus deoxidized copper pipe for...

Страница 7: ...the outside causes water leak Flow Selector unit Heat insulating pipe Attached Binding band Local supply Heat insulator The upper slit 6 ELECTRIC WORK WARNING 1 Using the specified wires ensure to connect the wires and fix wires securely so that the external strength of the wires do not transmit to the connecting part of the terminals Incomplete connection or fixation may cause fire etc 2 Be sure ...

Страница 8: ...pinched and then attach the cover RBM Y1123FE RBM Y1803FE RBM Y2803FE Cord clamp Control wiring Attached wire Control wire Attached wire Power supply CN02 Green CN01 Red Earth screw Fixing screw 4 parts Earth screw Cord clamp Attached wire Power supply CN01 Red Control P C board Control P C board Fixing screw 4 parts CN02 Green Cord clamp System wiring diagram Power supply Single phase 220 240V 50...

Страница 9: ...ttached wire power supply Then check the R L and S N phases and connect the wire and the lead wires with the attached wire joints Connect the ring terminal of the attached wire power supply to the earth screw Connect the connector Black of the attached wire control wiring to CN081 on the indoor P C board Secure the two attached wires with the attached cord clamp Be careful not to apply tension to ...

Страница 10: ...tor unit NOTE 1 way Air Discharge Cassette Type MMU AP SH Series wiring refer to the Under Ceiling Type page 11 1 way Air Discharge Cassette Type MMU AP YH Series Floor Standing Type MMF AP H Series R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Indoor P C board CN081 Attached wire Power supply Cord clamp Attached wire Control wiring Earth screw for Flow Selector unit Faston connec...

Страница 11: ...LECTRIC WORK 1 way Air Discharge Cassette Type MMU AP SH Series Indoor P C board R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Attached wire Power supply Power supply Cord clamp Cord clamp CN081 Black Earth screw for Flow Selector unit Earth screw Faston connection R L S N terminal block for power supply Attached wire Control wiring Under Ceiling Type MMC AP 7H Series CN81 Black I...

Страница 12: ...e front panel 3 Slightly open the lower part of the front panel and then pull the upper part of the front panel toward you to remove it from the rear plate 4 Remove the terminal cover and the clamp base 5 Insert the control wire fully into the control wired remote controller terminal block and secure it tightly with screws 6 Connect the control wire connector of the flow selector unit to the lead ...

Страница 13: ...k Cord clamp R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Indoor P C board CN081 Attached wire Control wiring Earth screw for Flow Selector unit Faston connection R L S N terminal block for power supply Attached wire Power supply Cord clamp Power supply Earth screw Air to Air Heat Exchanger with DX Coil Unit MMD VN HEXE Series 6 ELECTRIC WORK Attached wire Power supply Attached w...

Страница 14: ... control wire 8 Clamp the power supply wire with the cord clamp 9 Attach the terminal cover with a screw 10 Take the control wire out of the cable slot on the rear panel so that it produces about 600 mm from the front 11 Remove the terminal cover UP 12 Remove the LED BASE 13 Insert the control wire fully into the control Wired remote controller terminal block and secure it tightly with screws 14 C...

Страница 15: ...nge SET DATA to 01 by the timer buttons 4 Push SET button 5 Push TEST button Then the setup finished Incorrect example of connection When connecting the multiple indoor units to a single FS unit the indoor units which are connected with the multiple FS units are unavailable for the group control by a single remote controller For the indoor unit a remote controller cannot be individually connected ...

Страница 16: ...893801 2 TOSHIBA C TOSHIBA C TOSHIBA C TOSHIBA C TOSHIBA CARRIER CORPORA ARRIER CORPORA ARRIER CORPORA ARRIER CORPORA ARRIER CORPORATION TION TION TION TION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...

Отзывы: