Registor
address
Read/Write
Data
Byte
Data Definition and remarks
Holding Registor
40001
R/W
Operation / stop setting
2 0: STOP 1: OPERATE
40002
Operation mode setting
2
1: HEATING MODE 2: COOLING MODE 3: DRY MODE
40003
Set temperature setting
2 10 times values
40004
Automatic cooling set temperature (Dual set point) setting
2 10 times values
40005
Automatic heating set temperature (Dual set point) setting
2 10 times values
40006
Fan speed setting
2
1: FAN STOP 2 : FAN AUTO 3 : FAN SPEED [HH]
4 : FAN SPEED [H] 5 : FAN SPEED [L]
40007
Operation prohibition setting
2
bit0 : Operation STOP
bit1: Operation Mode
bit2 : temperature setting
bit4 : FAN
40008
Analogue Input Capacity Control*
2 0~15
40009~40019
Reserved
40020
CN90 DI1(Safty contact input)
2 0:OFF 1:ON
40021
CN90 DI2(External error input)
2 0:OFF 1:ON
40022
CN90 DI3(Forced Thermo OFF input)
2 0:OFF 1:ON
40023
CN90 DI4(Notice input)
2 0:OFF 1:ON
Registor
address
Read/Write
Data
Byte
Data Definition and remarks
Input Registor
30001
R
Operation / stop setting
2 0: STOP 1: OPERATE
30002
Operation mode setting
2
1: HEATING MODE 2: COOLING MODE 3: DRY MODE
30003
Set temperature setting
2 10 times values
30004
Automatic cooling set temperature (Dual set point) setting
2 10 times values
30005
Automatic heating set temperature (Dual set point) setting
2 10 times values
30006
Fan speed setting
2
1: FAN STOP 2 : FAN AUTO 3 : FAN SPEED [HH]
4 : FAN SPEED [H] 5 : FAN SPEED [L]
30007
Operation prohibition setting
2
bit0 : Operation STOP
bit1: Operation Mode
bit2 : temperature setting
bit4 : FAN
30008
Analogue Input Capacity Control*
2 0~15
30009~30019
Reserved
30020
CN90 DI1(Safty contact input)
2 0:OFF 1:ON
30021
CN90 DI2(External error input)
2 0:OFF 1:ON
30022
CN90 DI3(Forced Thermo OFF input)
2 0:OFF 1:ON
30023
CN90 DI4(Notice input)
2 0:OFF 1:ON
30024~30039
Reserved
30040
TC1
2 10 times values
30041
TC2
2 10 times values
30042
TC
2 10 times values
30043
TA
2 10 times values
30044
TF
2 10 times values
30045
Tx (auxiliary temperature sensor)
2 10 times values
30046
TO
2 10 times values
30047~30059
Reserved
30060
Alarm Code
2 For example : remote controller display 「E04」→「0x0044」
30061
Notice code1
2 For example : remote controller display 「201」→「129」
30062
Notice code2
2 For example : remote controller display 「201」→「129」
30063
Notice code3
2 For example : remote controller display 「201」→「129」
30064
Notice code4
2 For example : remote controller display 「201」→「129」
30065
Notice code5
2 For example : remote controller display 「201」→「129」
30066
Thermostat On Digital Output
2 0:OFF 1:ON
30067
Cooling operation signal output / secondary heating signal output
2 0:OFF 1:ON
30068
Heating operation signal output
2 0:OFF 1:ON
30069
Fan Moter Digital Output
2 0:OFF 1:ON
30070
Operating output
2 0:OFF 1:ON
30071
Outdoor unit(s) operation level is lower than capacity command
2 0:OFF 1:ON
30072
Outdoor unit(s) operation level is higher than capacity command
2 0:OFF 1:ON
*There are possibilities of thermodynamic and/or mechanical limitation from many factors. which may affect our system's heat pump cycle
(refrigerant cycle) during operation. Hence, there is a possibility that the capacity output may be different from capacity control setting.
P45
Содержание RBM-A101UPVA-E
Страница 21: ...P19 ...
Страница 45: ...9 Cable specifications P43 ...
Страница 46: ...10 Modbus setting method P44 ...
Страница 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Страница 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Страница 52: ...13 Wiring Diagram P50 ...
Страница 53: ...P51 ...
Страница 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...