7.7 DX COIL Guideline CO Pattern B
- Guideline Cooling Only Pattern B -
No. of Ref. Circuit by DX Coil Copper Tube Dia. and DX Coil Size (HP)
Min
Max
Min
Max
Min
Max
8 HP
12.0
10.0
6.0
10 HP
14.0
12.0
6.0
12 HP
16.0
12.0
8.0
14 HP
20.0
14.0
8.0
16 HP
22.0
16.0
10.0
18 HP
24.0
18.0
10.0
20 HP
26.0
20.0
12.0
22 HP
30.0
22.0
12.0
24 HP
32.0
24.0
14.0
26 HP
34.0
26.0
14.0
28 HP
38.0
26.0
14.0
30 HP
40.0
28.0
16.0
32 HP
42.0
30.0
16.0
34 HP
46.0
32.0
18.0
36 HP
48.0
34.0
20.0
38 HP
50.0
36.0
20.0
40 HP
54.0
38.0
22.0
* It is able to connect SMMS-e,u H/P model when you set it as Cooling only mode.
Please setup the Function CODE(DN code) [0F] : "0000" to "0001" by a wired remote controller.
HP
8
10
12
14
16
18
20
22
24
Std.
3,600
4,200
5,300
6,140
7,200
7,800
8,400
9,520
10,370
Min.
Max.
Min.
1,800
2,250
2,700
3,150
3,600
4,050
4,500
4,950
5,400
Max.
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
22.4
28.0
33.5
40.0
45.0
50.4
56.0
61.5
67.0
Coil on Air Temp.
15 - 32°CWB (18 - 43°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
33°CDB / 28°CWB
Max. Capacity (kW)
-
-
-
-
-
-
-
-
-
Coil on Air Temp.
-
Condensating Temp.
-
Sub Cooling
-
-
No
restriction
No
restriction
AHU Air
Flow rate
(m3/hr)
No restriction
No restriction
Number of Circuits
Copper
Tube
8.0mm
9.5mm
12.7mm
Air Suction Temp.
(Design temp)
H
ea
tin
g
Air Suction Temp.
(Design temp)
Dx Coil HP
No
restriction
DX Coil Internal
volume (cc)
C
oo
lin
g
P31
Содержание RBM-A101UPVA-E
Страница 21: ...P19 ...
Страница 45: ...9 Cable specifications P43 ...
Страница 46: ...10 Modbus setting method P44 ...
Страница 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Страница 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Страница 52: ...13 Wiring Diagram P50 ...
Страница 53: ...P51 ...
Страница 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...