– 13 –
To change all the indoor addresses from an arbitrary wired remote controller
(When the setup operation with automatic address has finished, this change is available.)
Contents :
Using an arbitrary wired remote controller, the indoor unit address can be changed for each same
refrigerant cycle line.
* Change the address in the address check/change mode.
(Operation while air conditioner stops)
Procedure
1
2
3
- 1
3
- 2
3
- 3
Display panel will flash as shown on the drawing below when pushing
SET
+
CL
+
TEST
buttons at the same time for 4 seconds or more.
Make sure that the displayed CODE No. is [10].
• If the displayed CODE No. is not [10], push
TEST
button to erase the
display and perform the setting again from the beginning.
(The commands from the remote controller cannot be received for
approximately 1 minute after pushing
TEST
button.)
(When executing group control, the indoor unit numbers that is displayed
first becomes the main unit.)
Every pushing
UNIT
LOUVER
button, the indoor unit numbers in the group
control are successively displayed. Select the indoor unit of which
setting is to be changed.
At this time, the fan of the selected indoor unit is turned on and LED
indicator on the indoor unit will light up and the locations of indoor units, of
which setting is to be changed, can be checked.
Specify the CODE No. [12] with the temperature [
/
] button.
(CODE No. [12] : System address)
Change the system address from [3] to [2] with the timer time
[
/
] button.
Push
SET
button.
If the display changes from flashing to being lit, the setting is completed.
(* Display may differ depending
on the model of indoor unit.)
Indoor unit numbers which had
been given prior to the setting
change will be displayed.
Description
INDOOR UNIT OPERATION WHEN CONNECTED TO MULTIPLE UNITS
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
3
- 3
4
- 3
5
- 3
3
- 1
4
- 1
5
- 1
3
- 2
4
- 2
5
- 2
6
2, 6
7
1
7
SETTING