7
RBCTBPTS SMART Touch Controller
Installation & Owners Manual
2.
3. Digital Input / Output
The digital input and output currently have no functionality.
2.
4. USB
The USB interface located behind the cover plate is used for configuration via a PC
and for upgrading the firmware.
2.
5. Ethernet
The
SMART Touch Controller is a 10/100Base-T half/full duplex device. It supports auto-
negotiation and also features auto-crossover (Auto-MDIX), allowing the use of either a
straight-through or crossover cable.
It does not currently support DHCP and will therefore require the IP address, gateway
address and subnet-mask configuring to match the host network it is attached to.
If the unit is only being accessed via the local network then set the gateway address
to be
the same as the IP address, otherwise enter the address of the appropriate gateway or
router.
Ensure that the correct USB driver has been installed prior to
connecting the
SMART Touch Controller to a PC.
1
Global disable
:
wh
en active, turns all units off and inhibits the remote controllers.
:
on
becoming inactive, removes the inhibits from the remote controllers only.
2
Global on
:
o
n becoming active, turns all units
ON
.
:
on
becoming inactive, turns all units
OFF
.
3
Not assigned
4
Not assigned
1
Any unit in alarm :
ac
tive when any unit present on the system returns an error code.
2
Any unit on
:
ac
tive when any unit on the system returns an 'O
N
' state.
3
Not assigned
4
Not assigned
Digital input 1 is permanently enabled and active 'open'.
All other inputs and outputs have an enable switch and a polarity selector.
Relay ratings are 24v @ 1amp
2.
3.1. Digital Inputs
2.
3.2. Digital Ouputs
2.
6. Firmware Updates *** IMPORTANT NOTICE ***
Please check our website on a regular basis to update controller software