Branch Kit Set 1:4
8
EN
EN
Additional Refrigerant Amount
<RAV-SM2244AT8, SM2804AT8 series>
Formula for Calculating Additional Refrigerant Amount
Do not remove the refrigerant even if the additional refrigerant amount becomes minus
result as a result of calculations by the following formula and operate the air conditioner as it
is.
Outdoor unit
Diameter of connecting pipe
(liquid side)
Amount of additional refrigerant
per meter (g/m)
1
2, 3
4
to 7
α
β
γ
SM2244
Ø12.7
Ø9.5
Ø6.4
80
40
20
SM2804
Ø12.7
Ø9.5
Ø9.5
80
40
40
Outdoor unit
Amount of additional refrigerant (g) =
Amount of refrigerant added for main pipe +
amount of refrigerant added for first branch
amount of refrigerant added for second branch piping
SM2244
α
×
( 1 – 28) +
β ×
( 2 + 3 – 4) +
γ ×
( 4 + 5 + 6 + 7)
SM2804
α
×
( 1 – 28) +
β ×
( 2 + 3 – 4) +
γ ×
( 4 + 5 + 6 + 7)
4
5
2
1
3
6
7
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit