-4-
Note 2:
When using a separately sold remote
controller sensor, set the sensor inside the
remote controller to OFF.
Requirements
When using the remote controller for the first
time, the initial operation after power on will
last for a while. This is not a fault.
<Initial turn on time>
Let the remote controller run for
about 5 minutes.
<Turn on time after the second turn on>
Let the remote controller run for
about 1 minute.
The address setting of the multi-split air
conditioners cannot be completed just by
turning on the power (“SETTING” always
flashes). You must perform the operation on
the outdoor interface circuit board to complete
the address setting. The remote controller
cannot be operated when setting the address.
It takes at most 10 minutes to set the address.
Remote controller test run setup
1. Press the ON/OFF button.
Turn off the air conditioner.
2. Press the timer off button and the “
△
”
set button at the same time for at least 10
seconds. The LCD display area shows
“TEST” and becomes test mode.
3. The test run shall be performed in heating
or cooling mode.
• During test run, “TEST” is displayed on
the LCD display.
• When “TEST” is displayed, the
temperature cannot be adjusted.
• During test run, the machine will bear
a considerable load; therefore, it is
advisable not to carry out a test run
unless necessary.
Note 1:
After power up, the outdoor unit will not
work within about 3 minutes; otherwise
the operation will stop.
4. After exiting the test run mode, press
the timer off button again to ensure that
“TEST” on the LCD display disappears.(The
remote controller has a 60-minute timer off
function to prevent continuous test run.)
Remote controller DN setting
1. Press the On/Off button to shut down the
air conditioner.
2. Hold down the menu button and the “
▽
”
setting button for at least 10s. The LCD
displays “SETTING” and the lower left
corner displays indoor unit address, e.g.
1-1.
After verifying the address, press the timer
off button to access the DN setting mode.
3. After accessing the DN setting mode, use
the menu keys to switch between DN code
and data. Flashing means editable state.
Use “
△
” and “
▽
” for setting. After this
is done, use the timer off button to save
the setting (this step is required for each
setting). After the setting is over, press the
On/Off button to exit the DN setting mode.
Note 1:
When in the DN setting mode, the fan
of the indoor unit will start working.
Before this, please make sure there
is no foreign matter around the fan
blades that may obstruct their normal
rotation and be cautious.
Remote controller state
monitoring mode
1. Hold down the menu button for 10s (in
either on or off state) to access the remote
controller state monitoring mode.
2. After verifying the address, press the timer
off button to access the state monitoring
mode. Use “
△
” and “
▽
”to select the
code to check data.
• Refer to the Installation Manual supplied
with the indoor unit or outdoor unit or
service manual for details about the
check code and data.
3. Press the On/Off button to return to the
normal display interface.