background image

– 16 –

EN

With a remote control-less system (group control)

Besides the switching method using the wired remote control as a way to establish the external static pressure, 
switching is also possible by changing over the DIP switch settings on the indoor P.C. board as shown in the 
following table.
* However, once the settings are changed, it is necessary to reset the SET DATA to 0000 that placing the DIP 

switch back to the factory default position and rewriting the SET DATA back to 0000 with wired remote control 

(sold separately).

• Change over the DIP switch on the indoor P.C. board, and select the desired setting.

DIP switch positions (SW01, SW02)

DIP switch 

position

SET DATA

0000

0001

0003

0006

External static 

pressure

Standard

 (Factory default)

High static Pressure 1

High static Pressure 2

Low static Pressure

SW01

SW02

SW01

SW02

OFF OFF

OFF OFF

1

2

ON
OFF

1

2

ON
OFF

SW01

SW02

OFF

ON

OFF OFF

1

2

ON
OFF

1

2

ON
OFF

SW01

SW02

OFF OFF

OFF ON

1

2

ON
OFF

1

2

ON
OFF

SW01

SW02

OFF

ON

OFF ON

1

2

ON
OFF

1

2

ON
OFF

Filter sign setting

According to the installation condition, the filter sign 
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [01].

• For the [SET DATA] in Procedure 

4

, select the SET 

DATA of filter sign term from the following table.

To secure better effect of 
heating

When it is difficult to obtain satisfactory heating due to 
installation place of the indoor unit or structure of the 
room, the detection temperature of heating can be 
raised. Also use a circulator or other machinery to 
circulate heat air near the ceiling.
Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [06].

• For the set data in Procedure 

4

, select the SET 

DATA of shift value of detection temperature to be 
set up from the following table.

Remote control sensor

The temperature sensor of the indoor unit senses room 
temperature usually. Set the remote control sensor to 
sense the temperature around the remote control.
Select items following the basic operation procedure 
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• Specify [32] for the CODE No. in Procedure 

3

.

• Select the following data for the SET DATA in 

Procedure 

4

.

When 

 flashes, the remote control sensor is 

defective.
Select the SET DATA [0000] (not used) or replace the 
remote control.

SET DATA

Filter sign term

0000

None

0001

150 H

0002

2500 H

(Factory default)

0003

5000 H

0004

10000 H

SET DATA

Detection temperature shift value

0000

No shift

0001

1.8 °F (+1 °C)

0002

3.6 °F (+2 °C)

(Factory default)

0003

5.4 °F (+3 °C)

0004

7.2 °F (+4 °C)

0005

9.0 °F (+5 °C)

0006

10.8 °F (+6 °C)

SET DATA

0000

0001

remote control 

sensor

Not used 

(Factory default)

Used

31-EN

32-EN

+00EB99810201_01EN.book  Page 16  Wednesday, June 1, 2016  2:52 PM

Содержание RAV-SP181BT-UL

Страница 1: ...For commercial use Pour usage commercial Indoor Unit Model name Concealed Duct Type RAV SP181BT UL RAV SP241BT UL RAV SP301BT UL RAV SP361BT UL RAV SP421BT UL AIR CONDITIONER SPLIT TYPE Installation Manual 00EB99810201_01EN book Page 1 Wednesday June 1 2016 2 52 PM ...

Страница 2: ... different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for t...

Страница 3: ...e sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connec...

Страница 4: ...encies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation ...

Страница 5: ...opening size C 29 5 750 41 3 1050 55 1 1400 Space required for attaching or detaching the filter D 28 7 730 23 6 600 40 5 1030 Electrical control box Air filter locally procured 5 9 150 Ceiling opening size 15 5 400 Min 1 Air discharge Ceiling opening size C Electrical control box Check port A 17 7 17 7 450 450 Air discharge 5 9 150 or more Air intake 1 2 30 Ceiling Ceiling Unit width 31 5 800 Cei...

Страница 6: ...dle it with plastic band at positions other than specified To install vibration isolation material to hanging bolts confirm that it does not increase the unit vibration External dimensions Unit in mm CORRECT INCORRECT INCORRECT 1 room Hanging bolt 4 M0 4 10 locally procured Hanging bolt pitch B Unit external dimension A Air discharge flange outside C 5 5 140 1 7 44 1 9 49 Outside 8 6 218 2 5 8 147...

Страница 7: ...allation of the wired remote control refer to the instructions that are supplied with the control The connection point for the control wiring and the entrance point for the control wiring are clearly marked in the instructions Hanging bolt W3 8 M10 4 pieces Nut W3 8 M10 12 pieces Nut W3 8 M10 M10 flat washer Accessory M10 flat washer Accessory Hanging bolt W3 8 M10 Nut W3 8 M10 Set the air intake ...

Страница 8: ...High 0 15 in WG Standard Air Flow 706 cfm 241 type Mid Low 650 700 750 800 850 900 95010001050110011501200 0 45 0 50 0 30 0 35 0 40 0 45 0 15 0 20 0 25 0 30 0 00 0 05 0 10 0 15 Air flow cfm External Static Pressure in WG High 0 46 in WG High 0 35 in WG High 0 25 in WG High 0 15 in WG Mid Low Standard Air Flow 953 cfm 301 type 0 45 0 50 0 30 0 35 0 40 0 15 0 20 0 25 0 00 0 05 0 10 850 900 950100010...

Страница 9: ...0 15 in WG Standard Air Flow 706 cfm 241 type Mid Low 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 650 700 750 800 850 900 95010001050110011501200 Air flow cfm External Static Pressure in WG High 0 46 in WG High 0 35 in WG High 0 25 in WG High 0 15 in WG Mid Low Standard Air Flow 953 cfm 301 type 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 850 900 95010001050110011501200125013...

Страница 10: ...iece 12 18 1 1 piece 12 25 1 1 piece D H 12 6 320 Remove this cover to install filters in the filter rack Replace the cover after the filters are installed Filter rack W All unit models have the FR 1 FR 2 filter position option available Both positions use the same filters per model shown in the chart above Two positions for filter rack FR 1 FR 2 Indoor unit FR 1 Back air intake flange FR 2 Under ...

Страница 11: ...as shown in the following figure Do not provide any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe Connecting drain pipe Insert the drain socket into the connector until the socket can go no farther REQUIREMENT Connect the hard vinyl chloride pipes certainly so that water does not leak by using ad...

Страница 12: ...s running Check whether the water is draining from the drain pipe connecting port and check that no water is leaking from the drain pipe After checking that the water drains and there are no water leaks turn off the power connect the float switch connector to its original location CN80 on the printed circuit board and return the electrical control box to its original position When gravity drainage...

Страница 13: ...0A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle Align the centers of the connecting pipes and tighten the flare nut as far as possible with your finge...

Страница 14: ...se the power cord and control wire of specified thickness type and protective devices required Do not connect 208 230 V power to the terminal blocks U3 U4 A B etc for control wiring Otherwise the system will fail Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulting in an accident Do not turn on the circuit breaker...

Страница 15: ... Secure the ground wire with the ground screw 4 Fix the wires with a cord clamp Unit in mm CAUTION Firmly tighten the screws of the terminal block Keep the wire length as shown in figure below when it is connected to the terminal block Control wire hole Electrical control box cover Screw Screw Conduit connection hole 3 B S A 4 L L Ground screw Cord clamp Conduit pipe System interconnection wires a...

Страница 16: ...erefore install the wired remote control to change the settings Power on SETTING flashes SETTING goes out Remote control is available Approx 5 minutes Power on SETTING flashes SETTING goes out Remote control is available Approx 1 minutes 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the...

Страница 17: ...re 4 select the SET DATA of filter sign term from the following table To secure better effect of heating When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator or other machinery to circulate heat air near the ceiling Follow to the basic operation procedure 1 ...

Страница 18: ...cumulative operating hours x1 h F8 Indoor unit discharge air temperature 1 3 4 2 Group control Group control is not available with the supplied wireless remote control Use the optional wired remote control In case of group control for system of multiple units One remote control can control maximum 8 indoor units as a group In case of group control in single system For wiring procedure and wiring m...

Страница 19: ...played Indoor UNIT No before setup change is displayed Procedure 5 1 Using temp setup buttons specify CODE No 14 CODE No 14 Group address 2 Using timer time buttons change the SET DATA from 0001 to 0002 SET DATA Header unit 0001 Follower unit 0002 3 Push button In this time the setup finishes when the display changes from flashing to lighting Procedure 6 If there is other indoor unit to be changed...

Страница 20: ... Central control is not available with the supplied wireless remote control Use the optional wired remote control Wiring for central control The terminal block for central control wiring and is the same as that for optional wired remote control Connect the central control wire to the terminals and on the terminal block in the same way as the optional wired remote control For details refer to the I...

Страница 21: ...9 or less refrigeration systems when used together with the SMMS series the number of refrigeration systems of the SMMS series is included Since all line addresses are set to 1 except for group control by the automatic address setup function after system power on change the line addresses for each refrigeration system using the wired remote control NOTE For changing setting line addresses using th...

Страница 22: ...ter manual system change 9 Test run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L1 to L2 and the grounding If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activa...

Страница 23: ...ay disappears operate the air conditioner according to the following Confirmation of trouble history for confirmation Confirmation of trouble history When a trouble occurred on the air conditioner the trouble history can be confirmed with the following procedure The trouble history is stored in memory up to 4 troubles The history can be confirmed from both operating status and stop status Procedur...

Страница 24: ...M Outdoor unit P C board Outdoor Outdoor P C board In the case of EEPROM trouble Entire stop H01 Outdoor unit compressor breakdown Outdoor Current detect circuit power voltage Minimum frequency was reached in the current releasing control or short circuit current Idc after direct excitation was detected Wiring trouble of compressor open phase Entire stop H02 Outdoor unit compressor lock Outdoor Co...

Страница 25: ...ing etc was detected in the outdoor unit fan drive circuit Entire stop P26 ALT Outdoor unit inverter Idc activated Outdoor IGBT outdoor unit P C board inverter wiring compressor Short circuit protection for compressor drive circuit devices G Tr IGBT was activated Entire stop P29 ALT Outdoor unit position trouble Outdoor Outdoor unit P C board high pressure switch Compressor motor position trouble ...

Страница 26: ...EB99810201 00EB99810201_01EN book Page 46 Wednesday June 1 2016 2 52 PM ...

Отзывы: