� 5 �
9-EN
10-EN
WARNING
•
When the air conditioner cannot cool or heat a room well,
contact the dealer from whom you purchased the air
conditioner as refrigerant leakage is considered as the
cause.
In the case of repair that requires refill of refrigerant, ask
service personnel about details of the repair.
The refrigerant used in the air conditioner is harmless.
Generally, the refrigerant does not leak. However, if the
refrigerant leaks in a room and a heater or stove burner in the
room catches fire, it may generate toxic gas.
When you ask service personnel for repairing refrigerant
leakage, confirm that the leakage portion has been completely
repaired.
•
Do not install the air conditioner in a location that may be
subjected to a risk of exposure to a combustible gas.
If a combustible gas leaks and becomes concentrated around
the unit, a fire may occur.
•
Install the refrigerant pipe securely during the installation
work before operating the air conditioner.
If the compressor is operated with the valve open and without
the refrigerant pipe, the compressor sucks air and the
refrigeration cycle is over pressurized, which may cause a burst
or injury.
•
When carrying out the pump-down work, shut down the
compressor before disconnecting the refrigerant pipe.
Disconnecting the refrigerant pipe with the service valve left
open and with the compressor still operating will cause air, etc.
to be sucked in, raising the pressure inside the refrigeration
cycle to an abnormally high level, and possibly resulting in
rupturing, injury, etc.
WARNING
•
After installation work, make sure below before operation.
- Connection pipes are connected properly and no leakage.
- Packed valves are fully open.
Running compressor without open packed valves may cause
abnormal high pressure and parts failure.
Leakage at connection piping may suck air and make further high
pressure cause burst and injure.
CAUTION
•
Do not climb onto or place objects on top of the outdoor unit.
You may fall or the objects may fall off of the outdoor unit and
result in injury.
•
Wear heavy gloves during the installation work to avoid
injury.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
ground. If any section of pipe is buried, there must be a 6 in.
(152 mm) vertical rise to the valve connections on the outdoor units.
If more than the recommended length is buried, refrigerant may
migrate to the cooler buried section during extended periods of
system shutdown. This causes refrigerant slugging and could
possibly damage the compressor at start-up.
1131701101-00_S01_297x210_60p_S_p70_220426.indd 5
26/4/2565 11:41:09