2
INSTALLATION PROCEDURE
Installation diagram of indoor unit
4
Mounting screw
Hook
Pipe hole
Indoor unit
Thread
Weight
Pipe hole
Mounting screw
Installation
plate
Mounting the installation plate
For installation of the indoor unit.
0
80 100
100mm
100mm
180
55
65
170
120
Hook
Hook
When the installation plate is directly mounted on the wall
1. Securely fix the installation plate to the wall by screwing it through the upper and lower fixing holes.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in
the above figure.
3. Attach the installation plate horizontally to the wall.
CAUTION
When installing the installation plate with mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in personal injury and property damage.
∅
5 mm hole
Mounting screw
∅
4 x 25 mm
Clip anchor
(local parts)
Projection
15 mm or less
Anchor bolt
Indoor unit
65 mm or more
170 m
m
or m
ore
170 m
m
or m
ore
Installation plate
Hook
Air filter
Shield pipe
Insulate the refrigerant pipes
separately with insulation, not
together.
Hook
The auxiliary piping can be
connected to the left, rear left,
rear, right or bottom.
Right
Rear
Bottom
Rear left
Left
6 mm thick heat resisting
polyethylene foam
For the rear left and left piping
Insert the cushion between the
indoor unit and wall, and tilt the
indoor unit for better operation.
Wall
Do not allow the drain hose to get
slack.
Make sure to run the drain hose
sloped downward.
Cut the piping
hole sloped
slightly.