START
Has refrigerant recovery work been done?
YES
Remove the defective compressor.
Mount a service compressor.
Leakage check
Vacuuming
Charge the refrigerant.
END
Turn off the leakage breaker.
NO
Open PMV forcedly and then recover refrigerant
using a refrigerant recovery unit.
Never recover the refrigerant to the outdoor unit.
For the refrigerant recovery work during reinstallation
of repair work, be sure to use the refrigerant recovery unit.
Recovery of refrigerant to the outdoor unit is unavailable;
otherwise a serious accident such as explosion or
injury
may
be
caused.
1
1
. HOW TO EXCHANGE COMPRESSOR
1
1
-1. Exchanging Procedure of Compressor (Outline)
1
1
-2. Exchange of Compressor
For exchange of compressors, refer to (11) Compressor in Section of 13. Detachments.
–
7
4
–
SVM-13072.indb 95
SVM-13072.indb 95
11/01/13 1:53 PM
11/01/13 1:53 PM
Содержание RAV-SM304ATJP-E
Страница 17: ... 17 FILE NO SVM 14059 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SM304AT P SM404AT P ...
Страница 21: ... 21 FILE NO SVM 14059 4 WIRING DIAGRAM 4 1 RAV SM304AT P ...
Страница 22: ... 22 FILE NO SVM 14059 4 2 RAV SM404AT P ...
Страница 41: ... 41 FILE NO SVM 14059 7 2 Outdoor Print Circuit Board RAV SM304AT P SM404AT P MCC 1656 ...
Страница 84: ...FILE NO SVM 14059 13 EXPLODED VIEWS AND PARTS LIST 13 1 RAV SM304ATP E RAV SM304ATP TR 84 ...
Страница 86: ...FILE NO SVM 14059 Inverter assembly SM30 86 ...
Страница 88: ...FILE NO SVM 14059 13 2 RAV SM404ATP E RAV SM404ATP TR 88 ...
Страница 90: ...FILE NO SVM 14059 Inverter assembly SM40 90 ...
Страница 92: ...FILE NO SVM 14059 13 3 RAV SM304ATJP E 92 ...
Страница 94: ...FILE NO SVM 14059 Inverter assembly SM30 94 ...
Страница 96: ...FILE NO SVM 14059 13 4 RAV SM404ATJP E 96 ...
Страница 98: ...FILE NO SVM 14059 Inverter assembly SM40 98 ...