Item
3. Outdoor fan
motor control
Operation flow and applicable data, etc.
The blowing air volume at the outdoor unit side is controlled.
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
* For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the
fan motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
2) Fan speed
≥
400
when the motor stopped.
Air conditioner ON
(Remote controller)
YES
YES
NO
Indoor unit controller
NO
Fan motor ON
3) Fan lock
OFF status of
fan motor continues.
4) Motor operates as shown in the table below.
1) Outdoor unit
operation
command
(Outdoor
fan
control)
Air conditioner
OFF
Alarm
display
When To is abnormal
Outdoor fan speed (rpm)
Tap
SM30
f 0
0
f 9
600
f 1
200
f A
600
f 2
300
f B
650
f 3
370
f C
700
f 4
440
f D
700
f 5
440
f E
700
f 6
500
f F
700
f 7
550
f 8
600
Compressor speed (rps)
To
> 38°C
To > 28°C
To
To > 15°C
To > 5.5°C
To > 0°C
During
To > 38°C
ECO mode
To < 38°C
~ 13.8
~ 31.7
32.3 ~ MAX
MIN MAX MIN MAX MIN MAX
f 2
f 3
f A
f C
f D
f F
f 2
f 3
f 7
f A
f 9
f C
f 1
f 3
f 2
f 5
f 4
f 7
f 1
f 1
f 1
f 2
f 2
f 4
f 2
f 3
f B
f C
f C
f D
In cooling operation
Compressor speed (rps)
To > 15°C
To
To < 15°C
To < 5.5°C
To <
−
5.0°C
To > 15°C
During To < 15°C
ECO mode
To < 5.5°C
To <
−
5.5°C
When To is abnormal
~16.8 ~47.9 48.5 ~ MAX
f 3
f 8
f 9
f 3
f 9
f A
f 8
f A
f D
f B
f C
f D
f 3
f 3
f 6
f 3
f 3
f 8
f 5
f 9
f 9
f 7
f A
f B
f A
f B
f D
In Heating operation
f 2
f 3
f C
f D
f E
f F
To
<
0°C f 0 f 0 f 0
f 1 f 1 f 2
f D
f F
f D
f F
f F
f 2
f 3
f 2
f 3
f B
f C
f D
(for SM30)
Tap
SM30
Содержание RAV-SM304ATJP-E
Страница 17: ... 17 FILE NO SVM 14059 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SM304AT P SM404AT P ...
Страница 21: ... 21 FILE NO SVM 14059 4 WIRING DIAGRAM 4 1 RAV SM304AT P ...
Страница 22: ... 22 FILE NO SVM 14059 4 2 RAV SM404AT P ...
Страница 41: ... 41 FILE NO SVM 14059 7 2 Outdoor Print Circuit Board RAV SM304AT P SM404AT P MCC 1656 ...
Страница 84: ...FILE NO SVM 14059 13 EXPLODED VIEWS AND PARTS LIST 13 1 RAV SM304ATP E RAV SM304ATP TR 84 ...
Страница 86: ...FILE NO SVM 14059 Inverter assembly SM30 86 ...
Страница 88: ...FILE NO SVM 14059 13 2 RAV SM404ATP E RAV SM404ATP TR 88 ...
Страница 90: ...FILE NO SVM 14059 Inverter assembly SM40 90 ...
Страница 92: ...FILE NO SVM 14059 13 3 RAV SM304ATJP E 92 ...
Страница 94: ...FILE NO SVM 14059 Inverter assembly SM30 94 ...
Страница 96: ...FILE NO SVM 14059 13 4 RAV SM404ATJP E 96 ...
Страница 98: ...FILE NO SVM 14059 Inverter assembly SM40 98 ...