Outdoor Unit Installation Manual
EN
7
ELECTRICAL WORK
WARNING
1. Using the specified wires, ensure to connect
the wires, and fix wires securely so that the
external tension to the wires do not affect the
connecting part of the terminals.
Incomplete connection or fixation may cause a
fire, etc.
2. Be sure to connect earth wire. (grounding
work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for
telephone wires.
3. Appliance shall be installed in accordance
with national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fire.
CAUTION
• Wrong wiring may cause a burn-out to some
electrical parts.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core
and inner insulator of power and inter-connecting
wires when peeling them.
• Use the power and Inter-connecting wires with
specified thickness, specified type and protective
devices required.
• Remove the panel, and you can see electric
parts on the front side.
• A metal pipe can be installed through the hole
for wiring. If the hole size does not fit the wiring
pipe to be used, drill the hole again to an
appropriate size.
• Be sure to clamp the power wires and indoor/
outdoor connecting wires with banding band
along the connecting pipe so that the wires do
not touch the compressor or discharge pipe.
(The compressor and the discharge pipe
become hot.)
Furthermore, be sure to secure these wires with
the pipe valve fixing plate and cord clamps stored
in the electric parts box.
Wiring between Indoor
Unit and Outdoor Unit
The dashed lines show on-site wiring.
• Connect the indoor/outdoor connecting wires to
the identical terminal numbers on the terminal
block of each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire as
mentioned below.
Model RAV-
SM160
Power supply
220-240 V~, 50 Hz
Maximum running
current
32 A
Installation fuse rating
40 A
(all types can be used)
Power wire
H07 RN-F or 60245 IEC 66
(6.0 mm
2
or more)
Indoor/outdoor
connecting wires
H07 RN-F or 60245 IEC 66
(1.5 mm
2
or more)
Earth wire
H07 RN-F or 60245 IEC 66
(1.5 mm
2
or more)
Electric parts box
Pipe valve
fixing plate
Cord
clamp
Pipe hole
Panel
L
N
1
2
3
1
2
3
Input
power
(Main circuit)
(Indoor/outdoor
connecting wires)
Earth
Outdoor unit
Earth
Indoor unit
Remote
controller
Leakage
breaker
220-240 V~,
50 Hz
16-EN
+00EH99861901_01EN_Outdoor6HP_IM.book Page 16 Monday, June 2, 2008 6:00 PM