– 37 –
Heat insulation process
Apply heat insulation for the pipes separately at liquid side and gas side.
• For the heat insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 120
°C or higher.
• To use the attached heat insulation pipe, apply the heat insulation to the pipe connecting section of the indoor
unit securely without gap.
REQUIREMENT
• Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of
the pipe. (The pipe exposed to the outside causes water leak.)
• Wrap heat insulator with its slits facing up (ceiling side).
Indoor unit
Union
Heat insulation
pipe
(Accessory)
Flare nut
Heat insulator
of the pipe
Wrap the pipe with the attached heat insulator
without any gap between the indoor unit.
The seam must be faced upward
(ceiling side).
Banding band
(locally
procured)
8
Electrical connection
WARNING
•
Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces applied
to the terminals from affecting the terminals.
Incomplete connection or fixation may cause a fire or other trouble.
•
Connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.
•
Appliance shall be installed in accordance with national wiring regulations.
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.
CAUTION
• For power supply specifications, follow the Installation Manual of outdoor unit.
• Do not connect 220 – 240 V power to the terminal blocks (
,
) for control wiring.
Otherwise, the system will fail.
• Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires when
peeling them.
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
System interconnection wires specifications
*Number of wire x wire size
Remote controller wiring
CAUTION
The remote controller wire and system interconnection wires cannot be parallel to contact each other and cannot be
stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other factor.
System
interconnection
wires*
4 x 1.5 mm
2
or more
(H07 RN-F or 60245 IEC 66)
Up to
70 m
Remote controller wiring, remote controller inter-unit
wiring
Wire size: 2 × 0.5 to 2.0 mm
2
Total wire length of remote controller wiring and remote
controller inter-unit wiring = L + L1 + L2 + … Ln
In case of wired type only
Up to 500 m
In case of wireless type
included
Up to 400 m
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln
Up to 200 m
A
B
L1
L
L2
Ln
Indoor unit
Remote controller inter-unit wiring
Indoor unit
Indoor unit
Indoor unit
Remote
controller
(Max. 8 units)
Remote
controller
wiring
73-EN
74-EN